18.48.790 - CFC Appendix B, Table B105.2—Required fire flow for buildings other than one- and two-family dwellings, Group R-3 and R-4 buildings and townhouses.
Table B105.2 of Appendix B of the California Fire Code is amended to read as follows: TABLE B105.2 REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES AUTOMATIC SPRINKLER SYSTEM (Design Standard) | MINIMUM FIRE-FLOW (gallons per minute) | FLOW DURATION (hours) No automatic sprinkler system | Value in Table B105.1(2) | Duration in Table B105.1(2) Section 903.3.1.1 of the California Fire Code | 50% of the value in Table B105.1(2) a | Duration in Table B105.1(2) at the reduced flow rate Section 903.3.1.2 of the California Fire Code | 50% of the value in Table B105.1(2) b | Duration in Table B105.1(2) at the reduced flow rate