Sec. 37.159. - Backflow prevention assemblies.
(a) Approved backflow prevention assemblies. (1) Only backflow prevention assemblies approved by the California Department of Health Services shall be acceptable for installation by a water user connected to the city's potable water system. (2) The city will provide, upon request, to any affected customer a list of approved backflow prevention assemblies. (b) Backflow prevention assembly installation. (1) Backflow prevention assemblies shall be installed in a manner prescribed in Section 7603, Title 17 of the California Code of Regulations. Location of the assemblies should be as close as practical to the user's connection. The city shall have the final authority in determining the required location of a backflow prevention assembly. Approved backflow prevention assemblies shall be protected when necessary from extreme weather or site conditions that could cause physical damage to or malfunction of the backflow prevention assembly. a. Air-gap separation (AG). The air-gap separation shall be located on the user's side of and as close to the service connection as is practical. All piping from the service connection to the receiving tank shall be above grade and be entirely visible. No water use shall be provided from any point between the service connection and the air-gap separation. The water inlet piping shall terminate a distance of at least two (2) pipe diameters of the supply inlet, but in no case less than one inch above the overflow rim of the receiving tank. b. Reduced pressed principle backflow prevention assembly (RPA). The approved reduced pressure principle backflow prevention assembly shall be installed on the user's side of and as close to the service connection as is practical. The assembly shall be installed a minimum of twelve (12) inches above the grade and not more than thirty-six (36) inches above grade measured from the bottom of the assembly and with a minimum of twelve (12) inches side clearance. The assembly should be installed so that it is readily accessible for maintenance and testing. (c) Backflow prevention assembly testing and maintenance. (1) The owners of any premises on which, or on account of which, backflow prevention assemblies are installed, shall have the assemblies tested by a person who has demonstrated his or her competency on testing of these assemblies to the city. Backflow prevention assemblies must be tested at least annually and immediately after installation, relocation or repair. The city may require a more frequent testing schedule if it is deemed to be necessary. No assembly shall be placed back in service unless it is functioning as required. A report in a form acceptable to the city shall be filed each time an assembly is tested, relocated, or repaired. These assemblies shall be serviced, overhauled, or replaced whenever they are found to be defective, and all costs of testing, repair, and maintenance shall be borne by the water user. (2) The city will supply affected water users with a list of persons acceptable to the city to test backflow prevention assemblies. The city will notify affected customers by mail when annual testing of an assembly is needed and also supply users with the necessary forms which must be filled out each time an assembly is tested or repaired.
(Ord. No. 18-OR0118-1, § 2, 3-28-2018)
Ask a question about Oceanside law
Corpus searches the Oceanside sections it holds and shows the ones that match, with their citations. Free, no sign-in.