§ 6-8.910 — Where protection is required
City of Ontario, California, Municipal Code (2026 S-32: Current through Ordinance 3338, passed 7-21-2026) · Ontario Municipal Code § 6-8.910
Corpus is an independent public-information project, not the official City of Ontario website. Stable reference: corpuslaw.us/code/b7efb12b-efa2-402c-b1f8-3bd829e3251a
Sec. 6-8.910. Where protection is required.
Backflow protection for the City’s potable water supply shall be provided on each water service connection downstream of the water meter but before the structural dwelling to: (a) Premises having an auxiliary water supply such as recycled or non-potable water systems; (b) Premises on which any substance is handled in such fashion that could permit entry into the water system. This shall include the handling of process waters and waters originating from the City’s distribution system that have been subject to deterioration in sanitary quality; (c) Premises where there is any material dangerous to health which is handled in such a fashion as to create an actual or potential hazard. Examples of premises where actual, or potential, health hazards, or conditions will exist include, but are not limited to, the following: sewage treatment plants, sewage pumping stations, chemical manufacturing plants, hospitals, mortuaries, plating works, etc; (d) Premises that have pressurized equipment installed; (e) Premises that have landscape where potable water is used to irrigate; (f) Premises that have fire protection systems installed; (g) Premises that have internal cross-connections, unless such cross-connections are abated to the satisfaction of the City and approved by the state or local health agency; (h) Premises having intricate plumbing and piping arrangements or where not all portions of the premises are readily accessible for inspection purposes; (i) Premises having a repeated history of cross-connections being established or re-established; (j) Premises being served water through a temporary above ground water service connection; (k) Premises having a change in customer (either owner or tenant) on any commercial or industrial premise(s) where a backflow prevention assembly is not installed; the new or previous owner or customer shall notify the City immediately. The City will then reassess the level of protection required. Also, any alterations or improvements to existing onsite facilities that may affect the level of protection required must be reported immediately to the City to be evaluated; and (l) Premises that meet the definition of high-hazard cross-connection control premise under Appendix D of the Cross-Connection Control Policy Handbook. (§ 5, Ord. 3297, eff. March 18, 2025)
Ask a question about Ontario law
Corpus searches the Ontario sections it holds and shows the ones that match, with their citations. Free, no sign-in.