§ 15.24.025 — Amendments to the 2025 California Electrical Code
Municipal Code, City of Orange, California (through Ord. No. 01-26 adopted January 27, 2026) · Orange Municipal Code § 15.24.025
Corpus is an independent public-information project, not the official City of Orange website. Stable reference: corpuslaw.us/code/d8276138-23ac-42e9-98b6-91f681e8643a
§ 15.24.025: Amendments to the 2025 California Electrical Code.
310.3(B) Conductor Material is revised to add a second paragraph to read as follows: Copper wire shall be used for wiring No. 6 and smaller in all installations. Consideration for use of aluminum wiring can be made by the Building Official for feeder lines only on an individual basis where adequate safety measures can be ensured. 690.13(A) Location is revised to read as follows: The means to disconnect a photovoltaic and electrical energy storage system shall be installed at a readily accessible location on the exterior of the building. A visible-open, lockable AC disconnect shall be located within three feet of the meter, photovoltaic disconnect, or as required by the Building or Fire Code Official.
( Ord. 15-13 , 2013 ; Ord. 09-16 , 2016 ; Ord. 10-19 , 2019 ; Ord. 06-22 , 2022 ; Ord. 16-25 , 11/12/2025 )