Sec. 62-205. - Conservation devices.

(a) Any cooling or refrigeration system using water as a condensing medium shall be equipped with a water conservation device in accordance with accepted engineering practices, to discharge water from the condensing apparatus at the maximum practical temperature. (b) On an evaporative cooler of 5,000 CFM capacity or larger, recirculating pumps will be required to provide for the recirculating of water. (c) All precooling coils and water cooled condensing machines shall be equipped with pressure-actuated water control valves. (d) No discharge of water from any cooling or refrigeration system shall be greater than six gallons per minute.

(Code 1959, § 34-42; Ord. No. 1359, § 490(a))