§ 14.24.140 — Motor starting limitations—Three-phase
Municipal Code, City of Roseville, California · Roseville Municipal Code § 14.24.140
Corpus is an independent public-information project, not the official City of Roseville website. Stable reference: corpuslaw.us/code/5a5a07ba-2925-43bf-9641-966530815624
§ 14.24.140: Motor starting limitations—Three-phase.
A. Automatically controlled, three-phase motors shall comply with all applicable NEMA standards and shall have maximum locked rotor currents not in excess of the following: 1. 770 amperes at 208 volts; 2. 673 amperes at 240 volts; 3. 337 amperes at 480 volts. Maximum permissible current values listed apply to the installation of a single motor. B. Manually controlled, three-phase motors shall comply with all applicable NEMA standards and shall have maximum locked rotor currents not in excess of the following: 1. 1554 amperes at 208 volts; 2. 1346 amperes at 240 volts; 3. 673 amperes at 480 volts; 4. 135 amperes at 2400 volts; Maximum permissible current values listed apply to an installation of a single motor. C. Three-phase motors to be used for large loads or when special conditions exist may have locked rotor currents in excess of those allowed by subsections A and B of this section, upon approval of the superintendent. D. Motors having maximum locked rotor currents exceeding those stated in subsections A and B of this section, may be operated if used in conjunction with current-limiting devices designed to limit the starting current to the above-specified maximum values. E. Current-limiting devices may be omitted on the smaller motors of a group installation where such omission will not result in a starting current in excess of the allowable starting current of the largest motor in the group.
( Prior code § 8.42(e) (2) ; Ord. 1299 § 1, 1975 )
Ask a question about Roseville law
Corpus searches the Roseville sections it holds and shows the ones that match, with their citations. Free, no sign-in.