§ 15.100.280 — Auxiliary supervised annunciation

Sacramento City Code (current through Supplement No. 4, July 2026, and Ord. 2026-0022) · Sacramento City Code § 15.100.280

Corpus is an independent public-information project, not the official City of Sacramento website. Stable reference: corpuslaw.us/code/ff7e1baa-1b8d-4110-b332-821fb1283573

15.100.280 Auxiliary supervised annunciation.

An auxiliary supervised annunciation system shall be installed in the fire control room. A "trouble condition" in these systems shall be indicated by an audible signal and a visual display that clearly indicates the following: A. Low fuel status (when fuel level falls below minimum required amount) for: 1. Standby and emergency generator(s), and 2. Fire pump(s); B. Low water status of the auxiliary water supply (below minimum required amount); C. Fire pump(s) running; D. Generator(s) running; E. Fire department breathing air system. (Note: Where a trouble condition exists on any of the above items a system trouble shall be transmitted.) This may be integrated within the main fire alarm annunciator panel. (Prior code §§ 9.28.1227, 15.11.1108)