§ 17.12.030 — Aluminum Wiring
Municipal Code of the City of San Marcos, California (Codified through Ordinance No. 2026-1582, enacted September 22, 2026. (Supp. No. 14)) · San Marcos Municipal Code § 17.12.030
Corpus is an independent public-information project, not the official City of San Marcos website. Stable reference: corpuslaw.us/code/7467f3ee-691b-4301-b2fa-dbd768847b80
17.12.030 - Aluminum Wiring.
Article 310.3(B) is amended to read as follows: Copper wire shall be used for wiring No. 6 and smaller in all installations. Aluminum wiring may be approved by the City for feeder conductors only where adequate measures are taken to prevent oxidation of the aluminum wire. Aluminum conductors of No. 6 or smaller used for branch circuits shall require continuous inspection by an independent testing agency approved by the City for proper torquing of connections and installation of oxidation inhibitor at their termination point as required.
(Ord. No. 2019-1478, Exh. A, § 1.D, 10-22-2019; Ord. No. 2022-1526, § 1.D(Exh. A), 10-25-2022)
Ask a question about San Marcos law
Corpus searches the San Marcos sections it holds and shows the ones that match, with their citations. Free, no sign-in.