Sec. 8-2815. - Referenced standards (Chapter 44).
(a) NFPA 13, 2013 Edition, Installation of Sprinkler Systems is hereby amended as follows: (1) Section 6.8.3 is hereby amended as follows: 6.8.3 Fire department connections (FDC) shall be of an approved type. The FDC shall contain a minimum of two 2 ½" inlets. The location shall be approved and be no more than 150 feet from a public hydrant. The FDC may be located within 150 feet of a private fire hydrant when approved by the fire code official. The size of piping and the number of inlets shall be approved by the fire code official. If acceptable to the water authority, it may be installed on the backflow assembly. Fire department inlet connections shall be painted OSHA safety red. When the fire sprinkler density design requires 500 gpm (including inside hose stream demand) or greater, or a standpipe system is included, four 2 ½" inlets shall be provided. (2) Section 8.3.3.1 is hereby amended as follows: 8.3.3.1. When fire sprinkler systems are installed in shell buildings of undetermined use (Spec Buildings) other than warehouses (S occupancies), fire sprinklers of the quick-response type shall be used. Use is considered undetermined if a specific tenant/occupant is not identified at the time the fire sprinkler plan is submitted. Sprinklers in light hazard occupancies shall be one of the following: 1. Quick-response type as defined in 3.6.4.7 2. Residential sprinklers in accordance with the requirements of 8.4.5 3. Standard-response sprinklers used for modifications or additions to existing light hazard systems equipped with standard-response sprinklers 4. Standard-response sprinklers used where individual standard-response sprinklers are replaced in existing light hazard systems (3) Section 8.17.1.1.1 is hereby added as follows: 8.17.1.1.1 Residential Waterflow Alarms. A local water-flow alarm shall be provided on all sprinkler systems and shall be connected to the building fire alarm or water-flow monitoring system, where provided. Group R occupancies not requiring a fire alarm system by the California Fire Code shall be provided with a minimum of one approved interior alarm device in each unit. Sound levels in all sleeping areas shall be minimum of 15 DBA above the average ambient sound or a minimum of 75 DBA with all intervening doors closed, whichever is greater. Alarms shall be audible within all other living areas within each dwelling unit. When not connected to a fire alarm or water-flow monitoring system, audible devices shall be powered from an uninterruptible circuit (except for over-current protection) serving normally operated appliances in the residence. (4) Section 11.1.1.2 is hereby added as follows: 11.1.1.2 When fire sprinkler systems are required in buildings of undetermined use other than warehouses, they shall be designed and installed to have a fire sprinkler density of not less than that required for an Ordinary Hazard Group 2 use, with no reduction(s) in density or design area. Warehouse fire sprinkler systems shall be designed to Figure 16.2.1.3.2 (d) curve "G". Use is considered undetermined if a specific tenant/occupant is not identified at the time the sprinkler plan is submitted. Where a subsequent occupancy requires a system with greater capability, it shall be the responsibility of the occupant to upgrade the system to the required density for the new occupancy. (5) Section 11.2.3.1.1.1 is hereby added as follows: 11.2.3.1.1.1 The available water supply for fire sprinkler system design shall be determined by one of the following methods, as approved by the Fire Code Official: 1) Subtract the project site elevation from the low water level for the appropriate pressure zone and multiply the result by 0.433; 2) Use a maximum of 40 psi, if available; 3) Utilize the Orange County Fire Authority water-flow test form/directions to document a flow test conducted by the local water agency or an approved third party licensed in the State of California. (6) Section 23.2.1.1 is hereby revised as follows: Section 23.2.1.1 Where a waterflow test is used for the purposes of system design, the test shall be conducted no more than 6 months prior to working plan submittal unless otherwise approved by the authority having jurisdiction. (b) NFPA 13R 2013 Edition, Installation of Sprinkler System in Residential Occupancies up to and Including Four Stories in Height is hereby amended as follows: (1) Section 6.16.1 is hereby revised as follows: 6.16.1 A local water-flow alarms shall be provided on all sprinkler systems and shall be connected to the building fire alarm or water-flow monitoring system where provided. Group R occupancies containing less than the number of stories, dwelling units or occupant load specified in Section 907.2.8 of the 2010 California Fire Code as requiring a fire alarm system shall be provided with a minimum of one approved interior alarm device in each unit. Sound levels in all sleeping areas shall be a minimum of 15 dBA above the average ambient sound or a minimum of 75 dBA with all intervening doors closed, whichever is greater. Alarms shall be audible within all other living areas within each dwelling unit. When not connected to a fire alarm or water-flow monitoring system, audible devices shall be powered from an uninterruptible circuit (except for over-current protection) serving normally operated appliances in the residence. There shall also be a minimum of one exterior alarm indicating device, listed for outside service and audible from the access roadway that serves that building. (c) NFPA 13D 2013 Edition, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes is hereby amended as follows: (1) Section 4.1.3 is hereby added as follows: 4.1.3 Stock of Spare Sprinklers (2) Section 4.1.3.1 is hereby added as follows: 4.1.3.1. A supply of at least two sprinklers for each type shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (3) Section 4.1.5.2 [4.1.3.2] is hereby added as follows: 4.1.3.2 The sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property. (4) Section 4.1.3.3 is hereby added as follows: 4.1.3.3 The sprinklers shall be kept in a cabinet located where the temperature to which they are subjected will at no time exceed 100° F (38° C). (5) Section 4.1.3.4 is hereby added as follows: 4.1.3.4 A special sprinkler wrench shall be provided and kept in the cabinet to be used in the removal and installation of sprinklers. One sprinkler wrench shall be provided for each type of sprinkler installed. (6) Section 7.1.2 is hereby revised as follows: 7.1.2 The system piping shall not have a separate control valve unless supervised by a central station, or remote station alarm service (7) Section 7.6 is hereby deleted in its entirety and replaced as follows: 7.6 Alarms. Exterior alarm indicating device shall be listed for outside service and audible from the street from which the house is addressed. Exterior audible devices shall be placed on the front or side of the structure and the location is subject to final approval by the fire code official. Additional interior alarm devices shall be required to provide 55 dBA or 15 dBA above ambient, whichever is greater. Sound levels in all sleeping areas with all intervening doors closed shall be a minimum of 15 dBA above the average ambient sound level but not less than 75 dBA, whichever is greater. Audible devices shall be powered from an uninterruptible circuit (except for over-current protection) serving normally operated appliances in the residence. Exception: 1. When an approved water flow monitoring system is installed, interior audible devices may be powered through the fire alarm control panel. 2. When smoke detectors specified under CBC Section 907.2.11 are used to sound an alarm upon waterflow switch activation.
(Ord. No. NS-2851, § 41, 11-18-13)
Ask a question about Santa Ana law
Corpus searches the Santa Ana sections it holds and shows the ones that match, with their citations. Free, no sign-in.