Sec. 8-912. - Wiring Methods.

Section 230.43 of the California Electrical Code is amended to read as follows: 230.43 Wiring Methods for 1000 Volts, Nominal, or Less. Service entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods: (1) Open wiring on insulators (2) Type IGS cable (3) Rigid metal conduit (RMC) (4) Intermediate metal conduit (IMC) (5) Wireways (6) Busways (7) Auxiliary gutters (8) Rigid polyvinyl chloride conduit (PVC) (9) Cablebus (10) High density polyethylene conduit (HDPE) (11) Nonmetallic underground conduit with conductors (NUCC) (12) Reinforced thermosetting resin conduit (RTRC)

(Ord. No. NS-2905, § 11, 12-6-16)