§ 15.16.030 — Water Flow—Total Requirements Designated
Municipal Code, City of Santa Clarita, California (Santa Clarita Municipal Code current through legislation adopted 09-08-2026 (eCode360 publication SA4627, scraped 2026-11-18)) · Santa Clarita Municipal Code § 15.16.030
Corpus is an independent public-information project, not the official City of Santa Clarita website. Stable reference: corpuslaw.us/code/a7fb1a97-b458-4d95-ad3d-f7e3afaddbb7
§ 15.16.030: Water Flow—Total Requirements Designated.
The required total water flow for any given service area under consideration, or unit water system, shall be the sum of the minimum fire flow plus the maximum daily water flow requirements. The maximum daily water flow requirement shall be either two times or four times the average daily water flow requirement, depending on whether the water system is to be metered or unmetered. Qt equals Qf plus 2Qd for metered service; Qt equals Qf plus 4Qd for unmetered service. Qt equals the required total water flow in gallons per minute. Qf equals the minimum fire-flow water requirement in gallons per minute. Qd equals the average daily water flow requirement in gallons per minute, which is the sum of the residential or domestic water flow requirements plus the commercial, industrial, irrigation or other uses.
( Ord. 90-18 , 7/24/1990 )
Ask a question about Santa Clarita law
Corpus searches the Santa Clarita sections it holds and shows the ones that match, with their citations. Free, no sign-in.