For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 98.0206 — Mechanical Protection of Gas and Electric Equipment

San Diego Municipal Code (City Clerk PDFs, pages revised through October 2026) · San Diego Municipal Code § 98.0206

Corpus is an independent public-information project, not the official City of San Diego website. Stable reference: corpuslaw.us/code/955e3ee3-79c3-4809-9fcf-f87f062ee53a

§98.0206 Mechanical Protection of Gas and Electric Equipment

Where subject to physical damage from vehicular traffic or other causes, all gas or electric risers, regulators, meters, valves or other equipment shall be protected by concrete–filled three–inch galvanized steel pipe(s) encased in concrete to a minimum 30–inch depth below grade and extending to a minimum height of 42 inches above grade or three–inches above the highest equipment component, whichever is lower. The distance between the pipe(s) and closest component shall be not less than three inches. Posts shall be spaced to adequately protect the equipment; spacing shall not exceed 24 inches.

(“Mechanical Protection of Gas and Electric Equipment” added 9–30–1985 by O-16511 N.S.)