§ 15.12.150 — Standards of construction

Municipal Code, City of Temecula, California (legislation through Ord. No. 2026-04 adopted April 14, 2026) · Temecula Municipal Code § 15.12.150

Corpus is an independent public-information project, not the official City of Temecula website. Stable reference: corpuslaw.us/code/edd96d92-a30e-4d0c-9d25-943d95c0a32b

§ 15.12.150: Standards of construction.

In all areas of special flood hazards, all new construction and substantial improvements shall comply with the California Building Code (CBC) and the following standards: A. Anchoring. 1. All new construction and substantial improvements shall be adequately anchored to prevent flotation, collapse or lateral movement of the structure resulting from hydrodynamic and hydrostatic loads including the effects of buoyancy. 2. All manufactured homes shall meet the anchoring standards of Section 15.12.180 "Standards for manufactured homes." B. Construction Materials and Methods. 1. All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage. 2. All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage. 3. All new construction and substantial improvements shall be constructed with electrical, heating, ventilation, plumbing and air conditioning equipment and other service facilities that are designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding. 4. Require adequate drainage paths around structures on slopes to guide flood waters around and away from proposed structures. C. Elevation and Floodproofing. 1. All new residential and nonresidential construction and substantial improvements shall have the pad elevation elevated to a minimum of one foot above the FIRM base flood elevation. Prior to issuance of building permit, the pad elevation shall be certified by a registered professional engineer or surveyor. Upon completion of the structure, the elevation of the lowest floor, including basement, shall be certified by a registered professional engineer or surveyor. The certification shall be prepared on FEMA's Elevation Certification Form and submitted to the floodplain administrator. 2. All new residential and nonresidential construction and substantial improvements in Zone AO shall have the pad elevation elevated to a minimum of one foot above the highest adjacent grade elevation of the FIRM base flood elevation, or at least two feet if there is no FIRM base elevation of the adjacent grade. Prior to issuance of building permit, the pad elevation shall be certified by a registered professional engineer or surveyor. Upon completion of the structure, the elevation of the lowest floor, including basement, shall be certified by a registered professional engineer or surveyor. The certification shall be prepared on FEMA's Elevation Certification Form and submitted to the floodplain administrator. 3. Nonresidential construction shall either be elevated to conform with subsection (C)(1) or (C)(2) or together with attendant utility and sanitary facilities: a. Be floodproofed so that the structure is watertight with walls substantially impermeable to the passage of water; b. Have structural components capable of resisting hydrostatic and hydrodynamic loads and effects of buoyancy; and c. Be certified by a registered professional engineer or architect that the standards of this subsection have been satisfied. Such certifications shall be prepared on FEMA's standard form and submitted to the floodplain administrator. 4. Require (for all new construction and substantial improvements with fully enclosed areas below the lowest floor) that areas, usable solely for parking of vehicles, building access or storage, and in an area other than a basement, and which are subject to flooding, shall be designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwater. Designs for meeting this requirement must either be certified by a registered professional engineer or architect or meet or exceed the following minimum criteria: a. Either have a minimum of two openings with a total net area of not less than one square inch for every square foot of enclosed area subject to flooding, have the bottom of all openings no higher than one foot above grade (openings may be equipped with screens, louvers, valves or other coverings or devices provided that they permit the automatic entry and exit of floodwater); or b. Be certified by a registered professional engineer or architect in compliance to applicable floodproofing standards approved by FEMA. 5. Manufactured homes shall so meet the standards in Section 15.12.180 "Standards for manufactured homes." 6. Garages and Low-Cost Accessory Structures. a. Attached Garages. i. A garage attached to a residential structure, constructed with the garage floor slab below the base flood elevation (BFE) must be designed to allow for the automatic entry of flood waters. See subsection (C)(3). Areas of the garage below the BFE must be constructed with flood resistant materials. See subsection B. ii. A garage attached to a nonresidential structure must meet the above requirements or be dry-proofed. For guidance on below grade parking areas, see FEMA Technical Bulletin TB-6. b. Detached Garages and Accessory Structures. i. "Accessory structure" used solely for parking (two-car detached garages or smaller) or limited storage (small, low-cost sheds), as defined in Article II "Definitions," may be constructed such that its floor is below the BFE, provided the structure is designed and constructed in accordance with the following requirements: (A) Use of the accessory structure must be limited to parking or limited storage; (B) The portion of the accessory structure below the BFE must be built using flood-resistant materials; (C) The accessory structure must be adequately anchored to prevent flotation, collapse and lateral movement; (D) Any mechanical and utility equipment in an accessory structure must be elevated or flood-proofed to or above the BFE; (E) The accessory structure must comply with floodplain encroachment provisions in Section 15.12.200 "Floodways"; and (F) The accessory structure must be designed to allow for the automatic entry of flood waters in accordance with subsection (C)(3). ii. Detached garages and accessory structures not meeting the above standards must be constructed in accordance with the applicable standards in this section.

( Ord. 91-12 § 5.1 ; Ord. 13-05 § 4 )

Ask a question about Temecula law

Corpus searches the Temecula sections it holds and shows the ones that match, with their citations. Free, no sign-in.