Sec. 66-43. Appendix D—Fire Apparatus Access Roads.
The International Fire Code, Appendix D, is hereby amended to read as follows: D103.1 Access road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road, the minimum road width shall be 26 feet (7925 mm), exclusive of shoulders (see Figure D103.1). The dead-end fire apparatus access road turnaround 60' "Y" option shown in Figure D103.1 is repealed. D104.2 Buildings exceeding 62,000 square feet in area. Buildings or facilities having a gross building area of more than 62,000 square feet (5760 m2) shall be provided with two separate and approved fire apparatus access roads. D106.1 Projects having more than 100 dwelling units. Multiple-family residential projects having more than 100 dwelling units shall be equipped throughout with two separate and approved fire apparatus access roads.