§ 15-10-010 — Amendments to the International Mechanical Code

Municipal Code of the City and County of Broomfield, Colorado (Codified through Ordinance No. 2304, adopted May 26, 2026 (Supp. No. 54)) · Broomfield Municipal Code § 15-10-010

Corpus is an independent public-information project, not the official City of Broomfield website. Stable reference: corpuslaw.us/code/79a8b6f2-f8f1-45db-924b-cb3bf038c4d4

15-10-010 - Amendments to the International Mechanical Code.

The following amendments are hereby made to the 2024 International Mechanical Code: (A) Chapter 1 is hereby deleted. Refer to chapter 15-03, B.M.C., for administrative requirements. (B) Subsection 306.5.1, Sloped roofs, is amended by adding the following exception: EXCEPTION: This subsection shall not apply to Group R-3 occupancies. (C) Subsection 603.11 is amended by the addition of the following sentence: Appliances shall be connected to the duct system by means of an approved flexible connection, unless the building official waives such connection as unnecessary for protection against expansive soil movement. (D) Section 804.1 Direct vent terminations is hereby amended to read as follows: Vent terminals for direct-vent appliances shall be installed eighteen inches above grade or in accordance with manufacturer installation requirements, whichever is greater. (E) Section 918,2 Heat Pumps is hereby amended to read as follows: Electric heat pumps shall be tested in accordance with UL1995 or UL/CSA 60335-2-40. Electric heat pumps shall be installed at least twelve inches above grade or manufacturer installation requirements, whichever is greater. (F) 1109.2.5 Refrigerant pipe shafts is hereby amended to read as follows: Refrigerant piping that penetrates two or more floor/ceiling assemblies shall be enclosed in fire resistance rated shaft enclosures. The fire related shaft enclosure shall comply with Section 713 of the International Building Code. Exceptions: 1. Refrigerant systems using R-781 refrigerant (water) 2. Piping in direct refrigerant system where the refrigerant quantity does not exceed the amounts in Table 1103.1 for the smallest occupied space through which the piping passes. 3. Piping located on the exterior of the building where vented to the outdoors.

(Ord. 1858 §1, 2008; Ord. 1926 §14, 2011; Ord. 1994 §11, 2014; Ord. 2042 §11, 2017; Ord. No. 2115, 2-25-20; Ord. No. 2205, 3-7-23; Ord. No. 2295, § 6, 2-24-26)

Ask a question about Broomfield law

Corpus searches the Broomfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.