§ 15-12-010 — Amendments to the National Electrical Code
Municipal Code of the City and County of Broomfield, Colorado (Codified through Ordinance No. 2304, adopted May 26, 2026 (Supp. No. 54)) · Broomfield Municipal Code § 15-12-010
Corpus is an independent public-information project, not the official City of Broomfield website. Stable reference: corpuslaw.us/code/08f10b04-5e3d-4a3e-b31f-88727d80d706
15-12-010 - Amendments to the National Electrical Code.
The following amendments are hereby made to the National Electrical Code. The following amendment section numbers are based on the latest edition adopted by the State of Colorado, however the section numbers of subsequent NEC editions may change. The intent is to apply the following amendments regardless of changes to section numbers of subsequent editions. (A) NEC Section 230.70 (A) (1) is amended to read as follows: (1) Readily Accessible Location. The service disconnecting means shall be installed at a readily accessible location either outside of a building or structure or inside not greater than 2 feet from the point of entrance of the service conductors to the point the conductors enter the main service.
(Ord. 1926 §15, 2011; Ord. 1994 §12, 2014; Ord. No. 2115, 2-25-20)