§ 15-16-010 — Amendments to the International Fire Code

Municipal Code of the City and County of Broomfield, Colorado (Codified through Ordinance No. 2304, adopted May 26, 2026 (Supp. No. 54)) · Broomfield Municipal Code § 15-16-010

Corpus is an independent public-information project, not the official City of Broomfield website. Stable reference: corpuslaw.us/code/c6fe3e81-089d-4b6f-980a-c6d98621fabe

15-16-010 - Amendments to the International Fire Code.

The following amendments are hereby made to the 2024 International Fire Code which shall be referred to in this chapter 15-16 as the IFC: (A) Subsection 101.1, Title, of the IFC is amended to read as follows: 101.1 Title. These regulations shall be known as the Fire Code of the City and County of Broomfield, hereinafter referred to as "this code." (B) Subsection 102.7, Referenced codes and standards, of the IFC is amended by adding the following sentence: Where this code refers to the ICC Electrical Code, it means the latest edition of the National Electrical Code adopted by the State of Colorado. (C) Subsection 106.1, Submittals, of the IFC is amended to read as follows: 106.1 Submittals. Construction documents shall be submitted in one or more sets and in such form and detail as required by the fire code official. The construction documents shall be prepared by a registered design professional when said documents are submitted in support of an application for a construction permit required by Sections 105.6.1, 105.6.2, 105.6.3, 105.6.5, 105.6.6, 105.6.7, 105.6.8, 105.6.10, 105.6.11, 105.6.13, 105.6.20, 105.6.21, 105.6.22, 105.6.24, or 105.6.26. When requested, qualification statements shall be submitted to the fire code official for the registered design professional to demonstrate compliance with the professional qualifications defined in Section 202. (D) A new Subsection 106.2.5 of the IFC is added to read as follows: 106.2.5 Fire protection and life safety analysis. The fire code official may require the owner or agent to provide, without charge to the jurisdiction, a fire protection and life safety analysis prior to submitting construction drawings for high-rise buildings; covered mall buildings; buildings containing atriums connecting more than two stories; buildings containing high-piled combustible storage; Group A occupancies with an occupant load of 300 or more; Group H occupancies requiring a Hazardous Materials Management Plan and/or a Hazardous Materials Inventory Statement in accordance with Chapter 50; Groups I-2 and I-3 occupancies; any building, structure, or facility utilizing a performance-based approach to design in accordance with Section 104.2.3 or 104.2.4; and other structures or facilities as required by the fire code official. A fire protection and life safety analysis shall provide a description of the fire protection and life safety systems design for the proposed building or facility. This description shall include the basic concepts used for suppression, alarm, notification, egress, fire-resistive assemblies, smoke control, stair pressurization, and other related systems; as well as the coordination of those systems. Upon completion of the project, a copy of the approved documentation shall be maintained at the site and by the fire code official until demolition of the building or facility. The fire protection and life safety analysis shall: 1. Be prepared by a qualified engineer, specialist, laboratory, or fire safety specialty organization acceptable to the fire code official; 2. Bear the seal of a registered design professional; 3. Include a preliminary plan of the building, facility, or structure, drawn to scale upon suitable material; 4. Provide an analysis of fire protection water supplies for the building, facility, or structure, in accordance with Section 507; 5. Explain the intended use of the building, facility, or structure, or the applicable portions thereof, including special processes, the materials within the building, and the maximum height of any storage; 6. Describe all active and passive fire protection features of a specific facility, including, but not limited to, the basic concepts used for fire suppression, alarm, notification, egress, fire-resistive assemblies, smoke control, stair pressurization, and other related systems, as well as the coordination and integration of those systems with one another; and 7. Analyze the design, operation, use, coordination, and interaction of the fire-protection and life-safety systems. Prior to issuing operational or construction permits required by this code, the fire code official must determine, with reasonable certainty, that the fire protection and life safety features as documented in the fire protection and life safety analysis achieve minimum code compliance and provide the level of protection intended by this code. The fire code official shall specify the required organization, content categories, and format of the fire protection and life safety analysis. (E) Subsection 105.5.30(1) is amended to read as follows: 1. Storage and use of LP-gas in capacities exceeding 125 gallons (474 L) water capacity. (F) Subsection 105.5.51 Temporary membrane structures and tents, is amended to read as follows: 105.5.51 Temporary membrane structures and tents. An operational permit is required to operate an air-supported temporary membrane structure, a temporary special event structure or a tent having an area in excess of 400 square feet (37 m 2 ). (G) Subsection 105.5.58, Valet trash collection, of the IFC is added to read as follows: 105.5.58 Valet trash collection. An operational permit is required to provide valet trash and/or recycling services. (H) Subsection 105.6.7, Fire alarm and detection systems and related equipment, of the IFC is amended to read as follows: 105.6.7 Fire alarm and detection systems and related equipment. A construction permit is required for installation of or modification to fire alarm and detection systems and related equipment, including emergency alarm systems (Section 908). Maintenance performed in accordance with this code is not considered a modification and does not require a permit. (I) A new Subsection 105.6.26, Explosion control, of the IFC is added to read as follows: 105.6.26 Explosion control. A construction permit is required to install or modify explosion control provided as required in Section 911. (J) Subsection 105.6.16 LP-Gas is amended to read as follows: 105.6.16 LP-Gas. A construction permit is required for the installation or modification to an LP-gas system incorporating an individual container that exceeds a 125-gallon (474 L) water capacity. Maintenance performed in accordance with this code is not considered to be a modification and does not require a permit. (K) Subsection 105.6.21 Solar photovoltaic power systems is amended by the addition of the following exception: Exception: Photovoltaic power systems installed on detached, non-habitable Group U structures including, but not limited to, parking shade structures, carports, solar trellises, and similar structures shall not require the issuance of a construction permit by the District. (L) Subsection 105.6.25 Temporary membrane structures and tents, is amended to read as follows: 105.6.25 Temporary membrane structures and tents. A construction permit is required to erect an air-supported temporary membrane structure, a temporary special event structure or a tent having an area in excess of 400 square feet (37 m 2 ). Exceptions: 5. Tents used exclusively for recreational camping purposes 6. Funeral tents and curtains, or extensions attached thereto, when used for funeral services 7. Tents and awnings open on all sides, which comply with the following: 3.1. Individual tents shall have a maximum size of 700 square feet (65 m 2 ). 3.2. The aggregate area of multiple tents placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m 2 ) total. 3.3. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be maintained. 8. Temporary special event structures of 700 square feet (65 m 2 ) or less. (M) Subsections 108.2, 108.4, and 108.6 are amended by substituting the words "applicable governing authority" with "North Metro Fire Rescue District". (N) Subsection 109.2.1, Inspection requests, of the IFC is amended by adding the following sentence: Whenever any installation subject to inspection prior to use is required, the fire code official is authorized to require that every such request for inspection be filed not less than two business days before such inspection is desired. (O) Section 112, of the IFC, is deleted in its entirety and replaced with language to read as follows: SECTION 112 APPEALS 112.1 Appeals procedure - general. Any person, firm, or corporation aggrieved by any application, interpretation, or order made by fire district personnel pursuant to any provision of this code or the standards adopted herein may appeal such decision, interpretation, or order to the fire chief. The fire chief shall establish reasonable rules for such appeal and shall make a record of all proceedings. The decision of the fire chief shall be considered a final administrative decision. 112.2 Appeals procedure - administrative decisions. The authority to hear appeals of decisions of the fire chief, including the authority to determine the suitability of alternate materials and types of construction and to provide reasonable interpretations of the provisions of this code, shall be vested in the board of adjustment. The board of adjustment shall adopt reasonable rules and regulations for conducting its investigation and shall render decisions and findings in writing to the fire chief and the chief building official, with a duplicate copy to the appellant. (P) Subsection 113.4, Violation penalties, of the IFC is amended to read as follows: 113.4 Violation penalties. Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair, or do work in violation of the approved construction documents or directive of the fire code official, of a permit or certificate used under provisions of this code, shall be punishable as prescribed in chapter 1-12, B.M.C. Each day that a violation continues after due notice has been served shall be deemed a separate offense. (Q) Subsection 114.4, Failure to comply, of the IFC is amended to read as follows: 114.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable for such penalties as prescribed in chapter 1-12, B.M.C. (R) Section 202, General definitions, of the IFC is amended by defining "REGISTERED DESIGN PROFESSIONAL" to read as follows: REGISTERED DESIGN PROFESSIONAL. An engineer, licensed to practice professional engineering, as defined by the statutory requirements of the professional licensure laws of the State of Colorado, who shall be responsible and accountable to possess the required knowledge and skills to perform design, analysis, and verification in accordance with the provisions of this code and applicable professional standards of practice. (S) Section 202, General definitions, Occupancy Classification, of the IFC is amended by defining "Institutional Group I-1, Nine to 16 persons receiving custodial care" to read as follows: Nine to 16 persons receiving custodial care. A facility housing not fewer than nine and not more than 16 persons receiving custodial care shall be classified as Group R-4. (T) Section 202, General definitions, Occupancy Classification, of the IFC is amended by defining "Institutional Group I-1, Eight or fewer persons receiving custodial care" to read as follows: Eight or fewer persons receiving custodial care. A facility with eight or fewer persons receiving custodial care shall be classified as Group R-3 or shall comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or with Section P2904 of the International Residential Code. (U) Section 202, General definitions, Occupancy Classification, of the IFC is amended by defining "Institutional Group I-4, day care facilities, Eight or fewer occupants receiving care in a dwelling unit" to read as follows: Eight or fewer occupants receiving care in a dwelling unit. A facility such as the above within a dwelling unit and having eight or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy or shall comply with the International Residential Code. (V) Section 202, General definitions, of the IFC is amended by defining "Residential Group R-3" to read as follows: Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-4 or I, including: Buildings that do not contain more than two dwelling units Care facilities that provide accommodations for eight or fewer persons receiving care Congregate living facilities (nontransient) with 16 or fewer occupants Boarding houses (nontransient) Convents Dormitories Fraternities and sororities Monasteries Congregate living facilities (transient) with 10 or fewer occupants Boarding houses (transient) Lodging houses (transient) with five or fewer guestrooms and 10 or fewer occupants (W) Section 202, General definitions, Occupancy Classification, of the IFC is amended by defining "Residential Group R-3, Care facilities within a dwelling" to read as follows: Care facilities within a dwelling. Care facilities for eight or fewer persons receiving care that are within a single-family dwelling are permitted to comply with the International Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section P2904 of the International Residential Code. (X) Section 202, General definitions, Occupancy Classification, of the IFC is amended by defining "Residential Group R-4" to read as follows: Residential Group R-4. Residential Group R-4 shall include buildings, structures or portions thereof for more than eight but not more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. Buildings of Group R-4 shall be classified as one of the occupancy conditions indicated below. (Y) Subsection 4104.2 of the IFC is repealed in its entirety and reenacted to read as follows: 4104.2 Open-flame cooking devices. No gas-fired grills, charcoal grills, or other similar devices used for cooking, heating, or any other purpose, shall be used or kindled on any balcony or under any overhanging portion or within ten feet (3 m) of any structure. Exceptions: 1. One- and two-family dwellings, townhomes, and other structures built under the International Residential Code. 2. Where buildings, balconies and decks are protected by an automatic sprinkler system. 3. LP-gas burners having an LP-gas container with a water capacity not greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity]. Two extra 1 pound LP-gas containers may be stored on the balcony. 4. Listed natural gas appliances shall be permitted on balconies when installed in accordance with the International Fuel Gas Code and supplied by the building's natural gas system. 5. Listed electric ranges, grills, or similar electrical apparatus shall be permitted. (Z) Subsection 304.1.1, of the IFC is amended to read as follows: 304.1.1 Valet trash. Valet trash collection shall only be permitted in R-2 occupancies equipped with an automatic fire sprinkler system installed in accordance with IFC Section 903.3.1.1 or 903.3.1.2. Valet trash shall comply with the requirements of Appendix O as adopted. (AA) Subsection 311.5, Placards, of the IFC is deleted in its entirety. (BB) Subsection 504.3, Stairway access to roof, of the IFC is amended to read as follows: 504.3 Stairway access to roof. New buildings four or more stories above grade plane, except those with a roof slope greater than four units vertical in twelve units horizontal (33.3-percent slope), shall be provided with a stairway to the roof. When an exit enclosure is required by Section 1023, the stairway to the roof shall be located within an exit enclosure. Stairway access to the roof shall be in accordance with Section 1011.12. Such stairway shall be marked at street and floor levels with a sign indicating that the stairway continues to the roof. Where the roof is a vegetative roof, includes a landscaped roof area, or is used for other purposes, stairways shall be provided as required for such occupancy classification. (CC) Section 509.1, Identification, of the IFC is amended by adding the following sentence: "Letters, numbers, and directional arrows shall be white text on a red background." (DD) A new Section 509.1.2, Fire protection equipment identification, of the IFC is added to read as follows: 509.1.2 Fire protection equipment identification. Access to the fire sprinkler valve riser room and/or fire alarm control panel (FACP) shall be identified on the outside of the building with a minimum of four inch high letters or numbers with a ½" width stroke. Interior doors that access fire sprinkler valve rooms and/or FACPs shall utilize a minimum of two inch high letters with a ¼" stroke width. (EE) A new Section 511, Fire protection in recreational vehicle, mobile home, and manufactured housing parks, sales lots, and storage lots, of the IFC is added to read as follows: 511 Fire protection in recreational vehicle, mobile home, and manufactured housing parks, sales lots, and storage lots. Recreational vehicle, mobile home, and manufactured housing parks, sales lots, and storage lots shall provide and maintain fire hydrants and access roads in accordance with Sections 503 and 507. EXCEPTION: Recreational vehicle parks located in remote areas shall be provided with protection and access roadways as required by the fire code official. (FF) Subsection 903.2.6, Group I, of the IFC is amended by the addition of Exception 4: EXCEPTION 4: An automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be provided throughout all Group I-1 facilities that meet the federal Fair Housing Act definition of senior housing or housing for older persons. (GG) Exception 1 to Section 903.2.6 Group I is amended to read as follows: EXCEPTION 1: An automatic sprinkler system installed in accordance with Section 903.1.2 shall be permitted in Group I-1 Condition 1 facilities that do not meet the federal Fair Housing Act definition of senior housing or housing for older persons. (HH) Subsection 903.2.8.3, Care Facilities, of the IFC is amended to read as follows: An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in care facilities with eight or fewer individuals in a single-family dwelling. (II) A new subsection to 903.2.8, Group R, of the IFC is added to read as follows: 903.2.8.4 Group R-2. An automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be provided throughout all Group R-2 occupancies that meet the federal Fair Housing Act definition of senior housing or housing for older persons. (JJ) Subsection 903.2.11.1.3, Basements, is amended to read as follows: 903.2.11.1.3 Basements. Where any portion of a basement is located more than 75 feet (22860 mm) from openings required by Section 903.2.11.1, the basement shall be equipped throughout with an approved automatic sprinkler system. (KK) Subsection 903.3.1.2.1, Balconies and decks, is amended to read as follows: 903.3.1.2.1 Balconies and decks. Sprinkler protection shall be provided for exterior balconies, decks, and ground floor patios of dwelling units and sleeping units including all closets and usable storage spaces located thereto and accessed therefrom where either of the following conditions exist: Rest of code language stays the same (LL) Subsection 905.2, Installation standard, of the IFC is amended to read as follows: 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Fire department connections for standpipe systems shall be in accordance with Section 912. Fire hose is not required for any class of standpipe system. (MM) Subsection 907.2.4.2, Signs, of the IFC is amended to read as follows: 907.4.2.4 Signs. Where fire alarm systems are not monitored by a supervising station, an approved permanent sign shall be installed adjacent to each manual fire alarm box that reads: WHEN ALARM SOUNDS - DIAL 9-1-1. (NN) Subsection 907.5.2.1.1, Average sound pressure, of the IFC is amended by adding the following sentence: "The minimum sound pressure levels shall be: 75 dBA in occupancies in Groups R and I-1; 90 dBA in mechanical equipment rooms; and 60 dBA in other occupancies." (OO) Subsection 912.1, Installation, of the IFC is amended to read as follows: 912.1 Installation. Fire department connections shall be installed in accordance with this section and the NFPA standard applicable to the system design and shall comply with Sections 912.2 through 912.7. Unless the incorporation of the large diameter Storz-style connections is specifically approved by the Fire District, the number of 2.5-inch inlets provided shall not be less than one for each 250 gallons per minute of system demand or major fraction thereof, to a maximum of six 2.5-inch inlets. Each 2.5-inch inlet shall be equipped with a clapper valve to allow each hose to be connected and charged before the addition of more hoses. For fire department connections employing Storz-style connections, additional Storz connections shall only be required for manual systems with calculated hydraulic demands exceeding 750 gpm. In such situations, one Storz connection shall be provided for each 750 gpm of system demand, or major fraction thereof over 750 gpm. (PP) Subsection 1010.2.4(3)(3.1)) is amended to read as follows: 3.1 The locking device is readily distinguished as locked by the incorporation of a visual indicator (e.g., "locked," "closed," or other wording approved by the code official) on the egress side of the door. (QQ) The Exception to Section 1011.12 is deleted in its entirety. (RR) The Exception to Section 1011.12.2 is deleted in its entirety. (SS) Subsection 1101.1, Scope, of the IFC is amended to read as follows: 1101.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code. EXCEPTION: Buildings, portions of buildings, and life safety components therein, including the means of egress, that currently comply with the code under which constructed. (TT) Subsection 3105.2, Approval, is amended to read as follows: 3105.2 Approval. Temporary special event structures required to have a permit, as set forth in Sections 105.5 and 105.6, in excess of 700 square feet (65 m²) shall not be erected, operated or maintained for any purpose without first obtaining approval and a permit from the fire code official. (UU) Subsection 3108.8, Clearance, of the IFC is deleted in its entirety. (VV) Subsection 3401.1, Scope, is amended to read as follows: 3401.1 Scope. Tire rebuilding plants, tire storage in excess of 6' (1829 mm) in height or in excess of 1000 square feet (93 m 2 ) in area and tire byproduct facilities shall comply with this chapter, other applicable requirements of this code and NFPA 13. Tire storage in buildings shall also comply with Chapter 32. (WW) Section 5601.1.3, Fireworks, of the IFC is amended by deleting Exception 4. (XX) Subsection 5704.2.9.6.1, Locations where aboveground tanks are prohibited, of the IFC is amended to read as follows: 5704.2.9.6.1 Locations where aboveground tanks are allowed. Storage of Class I and II liquids in aboveground tanks outside of buildings is allowed when such storage complies with Sections 5704.2.9.6.1 through 5704.2.9.6.3. (YY) Subsection 5706.2.4.4, Locations where aboveground tanks are prohibited, of the IFC is deleted in its entirety. (ZZ) Subsection 6104.2, Maximum capacity within established limits, of the IFC, retaining the Exception as printed, is amended to read as follows: 6104.2 Maximum capacity within established limits. Within the City and County of Broomfield, the aggregate capacity of any one installation shall not exceed a water capacity of 2,000 gallons (7570 L). (AAA) The NFPA standards in Chapter 80, Referenced Standards, of the IFC are retained except as modified in the following table: NFPA Standards Standard reference number: | Change to: 11-21 | 11-24 12-22 | 12-25 12A-22 | 12A-25 13-22 | 13-25 13D-22 | 13D-25 13R-22 | 13R-25 14-22 | 14-24 17-21 | 17-24 17A-21 | 17A-24 20-22 | 20-25 24-22 | 24-25 31-20 | 31-24 33-21 | 33-24 34-21 | 34-24 35-21 | 35-26 40-22 | 40-25 52-22 | 52-26 58-23 | 58-24 59A-22 | 59A-23 69-23 | 69-24 72-22 | 72-25 76-20 | 76-24 80-22 | 80-25 92-21 | 92-24 105-22 | 105-25 110-22 | 110-25 111-22 | 111-25 170-21 | 170-24 204-21 | 204-24 260-23 | 260-24 286-23 | 286-24 303-21 | 303-26 318-22 | 318-25 326-20 | 326-25 400-22 | 400-25 410-20 | 410-25 505-23 | 505-24 655-19 | 655-17 770-21 | 770-26 780-23 | 780-26 853-20 | 853-25 855-20 | 855-23 1122-28 | 1122-26 1123-22 | 1123-26 1124-06 | 1124-26 1125-22 | 1125-26 2001-22 | 2001-25 2010-20 | 2010-25

(Ord. 1926 §16, 2011; Ord. 1935 §13, 2011; Ord. 1994 §13, 2014; Ord. 2042 §13, 2017; Ord. No. 2115, 2-25-20; Ord. No. 2138, § 8, 4-6-21; Ord. No. 2205, 3-7-23; Ord. No. 2295, § 8, 2-24-26)

Ask a question about Broomfield law

Corpus searches the Broomfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.