17-40-150 - General standards.
In all areas of special flood hazard, the following standards are required: (A) Anchoring. (1) All new construction and substantial improvements shall be anchored to prevent flotation, collapse, or lateral movement of the structure and capable of resisting the hydrostatic and hydrodynamic loads. (2) All manufactured homes must be elevated and anchored to resist flotation, collapse, or lateral movement, and capable of resisting the hydrostatic and hydrodynamic loads. Methods of anchoring may include, but are not limited to, use of over-the-top or frame ties to the ground anchors. This requirement is in addition to applicable state and local anchoring requirements for resisting wind forces. Specific requirements may include: a. Over-the-top ties must be provided at each of the four corners of the manufactured home, with two additional ties per side at intermediate locations, with manufactured homes less than fifty feet long requiring one additional tie per side; b. Frame ties must be provided at each corner of the home with five additional ties per side at intermediate points, with manufactured homes less than fifty feet long requiring four additional ties per side; c. All components of the anchoring system must be capable of carrying a force of 4,800 pounds; and d. Any additions to the manufactured home must be similarly anchored. (B) Construction materials and methods. (1) All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage. (2) All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage. (3) All new construction and substantial improvements shall be constructed with electrical, heating, ventilation, plumbing, and air conditioning equipment, and other service facilities that are designed or located so as to prevent water from entering or accumulating within the components during conditions of flooding. (C) Utilities. (1) All new and replacement water supply systems shall be designed to minimize or eliminate infiltration of flood waters into the system; (2) New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of flood waters into the systems and discharge from the systems into flood waters; and (3) On-site waste disposal systems shall be located to avoid impairment to them or contamination from them during flooding. (D) Properties removed from the floodplain by fill. A floodplain development permit shall not be issued for the construction of a new structure or addition to an existing structure on a property removed from the floodplain by the issuance of a FEMA Letter of Map Revision based on Fill (LOMR-F), unless such new structure or addition complies with the following: (1) Residential construction. The lowest floor (including basement), electrical, heating, ventilation, plumbing, and air conditioning equipment and other service facilities (including ductwork), must be elevated to one foot above the base flood elevation that existed prior to the placement of fill. (2) Nonresidential construction. The lowest floor (including basement), electrical, heating, ventilation, plumbing, and air conditioning equipment and other service facilities (including ductwork), must be elevated to one foot above the base flood elevation that existed prior to the placement of fill, or together with attendant utility and sanitary facilities be designed so that the structure or addition is watertight to at least one foot above the base flood level that existed prior to the placement of fill with walls substantially impermeable to the passage of water and with structural components having the capability of resisting hydrostatic and hydrodynamic loads of effects of buoyancy. (E) Standards for subdivision proposals. (1) All subdivision proposals including the placement of manufactured home parks and subdivisions shall be reasonably safe from flooding. If a subdivision or other development proposal is in a flood-prone area, the proposal shall minimize flood damage. (2) All proposals for the development of subdivisions including the placement of manufactured home parks and subdivisions shall meet floodplain development permit requirements of section 17-40-110 and the provisions of section 17-40-150. (3) Base flood elevation data shall be generated for subdivision proposals and other proposed development including the placement of manufactured home parks and subdivisions which is greater than fifty lots or five acres, whichever is the lesser, if not otherwise provided pursuant to section 17-40-060 or section 17-40-130. (4) All subdivision proposals including the placement of manufactured home parks and subdivisions shall have adequate drainage provided to reduce exposure to flood hazards. (5) All subdivision proposals including the placement of manufactured home parks and subdivisions shall have public utilities and facilities such as sewer, gas, electrical and water systems located and constructed to minimize or eliminate flood damage. (F) Standards for critical facilities. A critical facility is a structure or related infrastructure, but not the land on which it is situated, as specified in Rule 6 of the Rules and Regulations for Regulatory Floodplains in Colorado, that if flooded may result in significant hazards to public health and safety or interrupt essential services and operations for the community at any time before, during, and after a flood. (1) Classification of critical facilities. Critical facilities are classified under the following categories: Essential Services; Hazardous Materials; At-risk Populations; and Vital to Restoring Normal Services. It is the responsibility of the city engineer to identify and confirm that specific structures in the community meet the following criteria: a. Essential services facilities include public safety, emergency response, emergency medical, designated emergency shelters, communications, public utility plant facilities, and transportation lifelines. These facilities consist of: 1. Public safety (police stations, fire and rescue stations, emergency vehicle and equipment storage, and emergency operation centers); 2. Emergency medical (hospitals, ambulance service centers, urgent care centers having emergency treatment functions, and non-ambulatory surgical structures, but excluding clinics, doctor's offices and non-urgent care medical structures that do not provide these functions); 3. Designated emergency shelters; 4. Communications (main hubs for telephone, broadcasting equipment for cable systems, satellite dish systems, cellular systems, television, radio and other emergency warning systems but excluding towers, poles, lines, cables and conduits); 5. Public utility plant facilities for generation and distribution (hubs, treatment plants, substations and pumping stations for water, power and gas, but not including towers, poles, power lines, buried pipelines, transmission lines, distribution lines and service lines); and 6. Air transportation lifelines (airports [municipal and larger], helicopter pads and structures serving emergency functions, and associated infrastructure [aviation control towers, air traffic control centers, and emergency equipment aircraft hangars]). Specific exemptions to this category include wastewater treatment plants (WWTP), non-potable water treatment and distribution systems, and hydroelectric power generating plants and related appurtenances. Public utility plant facilities may be exempted if it can be demonstrated to the satisfaction of the city engineer that the facility is an element of a redundant system for which service will not be interrupted during a flood. At a minimum, it shall be demonstrated that redundant facilities are available (either owned by the same utility or available through an intergovernmental agreement or other contract) and connected, the alternative facilities are either located outside of the 100-year floodplain or are compliant with the provisions of this chapter, and an operations plan is in effect that states how redundant systems will provide service to the affected area in the event of a flood. Evidence of ongoing redundancy shall be provided to the city engineer on an as-needed basis upon request. b. Hazardous materials facilities include facilities that produce or store highly volatile, flammable, explosive, toxic and/or water-reactive materials. These facilities may include: 1. Chemical and pharmaceutical plants (chemical plant, pharmaceutical manufacturing); 2. Laboratories containing highly volatile, flammable, explosive, toxic and/or water-reactive materials; 3. Refineries; 4. Hazardous waste storage and disposal sites; and 5. Aboveground gasoline or propane storage or sales centers. c. Facilities shall be determined to be critical facilities if they produce or store materials in excess of threshold limits. If the owner of a facility is required by the Occupational Safety and Health Administration (OSHA) to keep a Material Safety Data Sheet (MSDS) on file for any chemicals stored or used in the work place, AND the chemical is stored in quantities equal to or greater than the Threshold Planning Quantity (TPQ) for that chemical, then that facility shall be considered to be a critical facility. The TPQ for these chemicals is: either 500 pounds or the TPQ listed (whichever is lower) for the 356 chemicals listed under 40 C.F.R. §302 (2010), also known as Extremely Hazardous Substances (EHS); or 10,000 pounds for any other chemical. This threshold is consistent with the requirements for reportable chemicals established by the Colorado Department of Health and Environment. OSHA requirements for MSDS can be found in 29 C.F.R. §1910 (2010). The Environmental Protection Agency (EPA) regulation "Designation, Reportable Quantities, and Notification," 40 C.F.R. §302 (2010) and OSHA regulation "Occupational Safety and Health Standards," 29 C.F.R. §1910 (2010) are incorporated herein by reference and include the regulations in existence at the time of the promulgation of Ordinance No. 1972, but exclude later amendments to or editions of the regulations. Specific exemptions to this category include: 1. Finished consumer products within retail centers and households containing hazardous materials intended for household use and agricultural products intended for agricultural use. 2. Buildings and other structures containing hazardous materials for which it can be demonstrated to the satisfaction of the local authority having jurisdiction by hazard assessment and certification by a qualified professional (as determined by the local jurisdiction having land use authority) that a release of the subject hazardous material does not pose a major threat to the public. 3. Pharmaceutical sales, use, storage, and distribution centers that do not manufacture pharmaceutical products. These exemptions shall not apply to buildings or other structures that also function as critical facilities under another category outlined in this article. d. At-risk population facilities include medical care, congregate care, and schools. These facilities consist of: 1. Elder care (nursing homes); 2. Congregate care serving twelve or more individuals (day care and assisted living); and 3. Public and private schools (pre-schools, K-12 schools, before-school and after-school care serving twelve or more children). e. Facilities vital to restoring normal services, including government operations. These facilities consist of: essential government operations (public records, courts, jails, building permitting and inspection services, community administration and management, maintenance and equipment centers). (2) Protection for critical facilities. All new and substantially improved critical facilities and new additions to critical facilities located within the special flood hazard area shall be regulated to a higher standard than structures not determined to be critical facilities. For the purposes of this subsection, protection shall include one of the following: a. Location outside the special flood hazard area; or b. Elevation or floodproofing of the structure to at least two feet above the base flood elevation. (3) Ingress and egress for new critical facilities. New critical facilities shall, when practicable as determined by the city council, have continuous non-inundated access (ingress and egress for evacuation and emergency services) during a 100-year flood event.
(Ord. 1972 §3, 2013)
Ask a question about Broomfield law
Corpus searches the Broomfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.