§ 14.10.040 — Local amendments to certain provisions of the International Fuel Gas Code

Municipal Code of Lakewood, Colorado (Supp. No. 15: codified through Ordinance No. O-2026-16, adopted April 27, 2026) · Lakewood Municipal Code § 14.10.040

Corpus is an independent public-information project, not the official City of Lakewood website. Stable reference: corpuslaw.us/code/091bfad3-73f3-47e6-9834-f6ad0e2abc0d

14.10.040 - Local amendments to certain provisions of the International Fuel Gas Code.

Certain provisions of the International Fuel Gas Code, as indicated in this section, are hereby amended. A. The provisions of Chapter 1 shall include the following amendments: 1. Subsection 101.1 is deleted. 2. Subsection 101.2 is amended by deleting the exception. 3. Section 103 is deleted. 4. Section 109 is replaced with the following: 109 Fees. Fees and valuation for permits required by this Code shall be specified in section 14.01.060 of the Lakewood Municipal Code. 5. Section 114 is replaced with the following: 114 Board of Appeals. Persons aggrieved under this Chapter 14.10 shall file an appeal with the Board of Appeals of the City of Lakewood as provided in Chapter 14.12 of the Lakewood Municipal Code. 6. Section 115.4 is deleted. B. The provisions of Chapter 3 shall include the following amendments: 1. Subsection 303.3 is amended by deleting exceptions 3 and 4. 2. A new subsection 305.13 is added to read as follows: 305.13 Roof mounted equipment. Equipment or appliances installed on a roof shall be a minimum of 12 inches above the roof on an approved or listed curb or platform. C. The provisions of Chapter 4 shall include the following amendments: 1. Subsection 404.6 is replaced with the following: 404.6 Underground penetrations prohibited. Gas piping shall not penetrate a building foundation wall below grade. When passing through masonry or concrete exterior walls, gas piping shall be encased with a protective pipe sleeve. The annular space between the gas piping and the sleeve shall be sealed to prevent the infiltration of water. 2. Subsection 404.12 is replaced with the following: 404.12 Minimum burial depth. Underground piping systems shall be installed a minimum depth of 12 inches below grade, except as provided in section 404.12.1. Underground plastic gas piping shall be installed a minimum of 18 inches below grade. 3. Subsections 406.4.1 and 406.4.2 are replaced with the following: 406.4.1 Test pressure and duration. Threaded gas piping shall be tested to 20 psi for 15 minutes. Welded or medium pressure gas piping shall be tested at 60 psi for 15 minutes. D. The provisions of Chapter 6 shall include the following amendments: 1. Subsection 621.1 is replaced with the following: 621.1 Unvented room heaters. Unvented gas burning appliances shall not be installed in any occupied building. 2. Subsection 623.2 is amended by adding an exception to read as follows: Exception: Commercial cooking appliances installed in accordance with the manufacturer's specifications for residential installation may be approved by the Building Official.

(Ord. O-2023-17 § 1, 2023; Ord. O-2022-18 § 1, 2022; Ord. O-2018-6 § 10, 2018; Ord. O-2011-10 § 10, 2011; Ord. O-2006-17 § 9, 2006; Ord. O-86-7 § 1, 1986; Ord. O-81-106 § 1, 1981)

Ask a question about Lakewood law

Corpus searches the Lakewood sections it holds and shows the ones that match, with their citations. Free, no sign-in.