13.06.080 - Fire systems.
A. An approved double check backflow prevention assembly shall be the minimum protection on all fire sprinkler systems using piping material that is not approved for potable water use or that does not provide for periodic flow-through. A reduced pressure backflow assembly must be installed if any solution other than the potable water can be introduced into the sprinkler system. B. All fire system assembly testing shall be in accordance with the Colorado Cross-Connection Control Manual, this Chapter 13.06, and the SOP Manual. Any conflict between the requirements set forth therein shall be resolved in favor of the more stringent requirement.