Sec. 4-3-2. - N.E.C. amendments.
(a) Section 230.70(A) of the N.E.C. is amended by the addition of a new Subparagraph (4), to read as follows: "(4) Meter Base. The length of service entrance conductors from the load side terminals of the meter base to the main disconnecting means shall be located immediately back to back, side to side, or top to bottom of the meter." (b) Section 110.26 of the N.E.C., Spaces About Electrical Equipment, is amended by the addition of a new Subparagraph (6)(B)(1), to read as follows: "(1) Above finish grade. Clearances shall be provided between bottom of panel and finish grade a minimum of twenty four (24) inches above finish grade." (c) Section 408.54 of the N.E.C. is amended by the addition of a new Paragraph (A) thereto, to read as follows: "(A) Additional Space in Panelboards. A new panelboard shall have sufficient ampacity and space for at least four (4) full-size circuit breakers for future usage."
(Ord. No. 6205, 6-9-97; Ord. No. 7031 §2, 8-11-03; Ord. No. 7437 §2, 1-23-06; Ord. No. 7892 §2, 10-14-08; Ord. No. 8456 §2, 3-26-12; Ord. No. 9250 §2, 4-9-18; Ord. No. 10685 §2, 4-8-24)