Sec. 13-209. - Means of egress from rooming units required.

Every rooming unit shall have access to two (2) or more safe, unobstructed means of egress, either by inside stairways or outside fire escapes, to safe and open space at ground level, as required by the laws of the state and of the city. Outside fire escapes shall be accessible through exit doors located as remotely as possible from inside stairways. All exit doors shall open outward, be equipped with panic hardware and have an exit light over them. All exits must comply with the state basic building code and the state fire safety code.

(Code 1970, § 13-9.18; Ord. of 4-82)