Sec. 9-9. - Fire protection water supply requirements.
(a) In accordance with NFPA 24 (2016), section 5.1.1, design of water-based suppression systems that are not supplied by fire pumps, shall be based on drought conditions of forty-five (45) psi static pressure as determined by the Boynton Beach Utilities Department. (b) New construction projects must provide the results of a hydrant flow test performed by the Fire Rescue Department, indicating a fire flow not less than one thousand five hundred (1,500) gpm @ twenty (20) psi above domestic use. This applies to new or existing hydrants within the required three hundred (300) feet of the facility. (c) Hydrants not in service (no water available) shall be covered with a black plastic bag so as not to be mistaken for active hydrants available for fire suppression. (d) All exterior fire protection piping must be painted red or a contrasting color from the building. (e) Water meters are prohibited on fire sprinkler supply lines.
(Ord. 18-008, § 3, 5-1-18; Ord. 20-036, § 2, 11-4-20)