Sec. 7-204. - Combustible gas systems.

Combustible gas detectors shall be installed for all new gas appliances and/or any renovations of an existing gas system. Where combustible gases are piped to an appliance, a combustible gas detection system with an external notification device and a key box as defined in section 7-20, shall be installed in accordance with NFPA 72. The external notification device shall provide audio and visual notification and have a sign not less than fourteen (14) inches × fourteen (14) inches stating, "combustible gas detected, call 911." The system shall be installed so that upon activation of the gas detection alarm, the gas supply shall automatically shut off.

(Ord. No. 2021-112, § 9, 9-13-21; Ord. No. 2025-108, § 2, 5-7-25)