§ 98-1991 — Emergency power
Code of Ordinances, City of Hialeah, Florida (Supp. No. 45: codified through Ordinance No. 2026-048, adopted June 23, 2026) · Hialeah Code of Ordinances § 98-1991
Corpus is an independent public-information project, not the official City of Hialeah website. Stable reference: corpuslaw.us/code/63ddb813-f447-4d43-8122-dbddd9e4c068
Sec. 98-1991. - Emergency power.
Supervisory residential care and treatment facilities, and community residential homes of seven persons or more shall provide an adequate fully operational emergency power source, and a supply of fuel sufficient to sustain the emergency power source for at least five days during a power outage, to power the facility to: (1) Power life safety equipment used or needed by the residents; (2) Consistently maintain an ambient air temperature of 81°F. or less within one or more areas of the facility having enough space to safely hold all of the facility's residents; and (3) Allow for the refrigeration and heating for preparation of food and beverages that are served by the facility to its residents, and for the storage of ice.
(Ord. No. 2019-025, § 1, 3-26-2019)
Ask a question about Hialeah law
Corpus searches the Hialeah sections it holds and shows the ones that match, with their citations. Free, no sign-in.