§ 179.017 — CRITICAL FACILITIES
Palm Bay City Code (2026 S-41) · Palm Bay City Code § 179.017
Corpus is an independent public-information project, not the official City of Palm Bay website. Stable reference: corpuslaw.us/code/7e835454-6885-4165-b605-34fe1eb28d31
§ 179.017 CRITICAL FACILITIES.
New critical facilities shall, to the extent feasible, be located outside of the special flood hazard area (one hundred (100)-year floodplain) and outside of the two-tenths percent (0.2%) annual chance flood hazard area (five hundred (500)-year floodplain). If documentation is provided that feasible sites outside of the special flood hazard are not available that satisfy the objectives of a proposed critical facility, then the critical facility shall: (A) Have the lowest floors elevated to or above the two-tenths percent (0.2%) annual chance flood hazard area (five hundred (500)-year floodplain) elevation plus one (1) foot (three hundred five (305) mm), or to the design flood elevation, whichever is higher; and (B) Meet the applicable flood resistant requirements of the Florida Building Code and ASCE 24, and where elevation requirements are specified, the minimum elevation shall be the two-tenths percent (0.2%) annual chance flood hazard area (five hundred (500)-year floodplain) elevation plus one (1) foot (three hundred five (305) mm), or to the design flood elevation, whichever is higher; and (C) Have access routes that are elevated to or above the two-tenths percent (0.2%) annual chance flood hazard area (five hundred (500)-year floodplain) elevation. (Ord. 2024-33, passed 9-19-24)