Sec. 13-225. - Extra hazardous occupancies.

When required by the Fire Marshal, extra hazardous occupancies shall comply with the following additional enumerated items. The Fire Marshal may accept equivalent protection measures. (1) The Fire Marshal shall provide at the property owner/operator's expense, a 24-hour-a-day security/fire watch on the property where the hazardous material is stored. (2) Impervious diking shall be required around all containers storing toxic and hazardous materials, with sufficient capacity within the containment area, to contain the full volume of the containers in the event of rupture. The property upon which the toxic and/or hazardous material is stored shall further be diked or otherwise safeguarded to the satisfaction of the Fire Marshal to prevent surface runoff of toxic materials or water, including contaminated fire suppression water or contaminated storm water, or other liquid which may contain toxic material from the site. (3) A complete deluge-type sprinkler system or other approved fire protection system shall be installed to protect all property, structures, outside storage containers, to dilute spilled material and to otherwise cool fires located upon the property. Yard fire hydrants with deluge pipes and automatic monitors shall be affixed and operational as a first aid measure for cooling any emergency that should develop upon the property. (4) In the event that water supply operating volumes and operating pressures are inadequate for the above protection, a fire pump with an automatic starting device shall be installed with adequate capacity and pressure to support the required system. In the event the water supply to the site is inadequate, the property owner/operator shall provide capacity to meet the protection demands of the site. (5) The Fire Marshal shall establish compliance schedules for both commencement and completion of the requirements established herein. Nothing contained herein shall exempt such property owner/operator/occupant from compliance with all other applicable portions of this chapter.

(Ord. No. 912-G, § 1(13-171), 1-8-2009)

Ask a question about St. Petersburg law

Corpus searches the St. Petersburg sections it holds and shows the ones that match, with their citations. Free, no sign-in.