§ 38-43 — Size vents for flammable liquid tanks

Code of Ordinances of the City of West Palm Beach, Florida (Supp. No. 77: codified through Ordinance No. 5172-26, enacted July 6, 2026) · West Palm Beach Code of Ordinances § 38-43

Corpus is an independent public-information project, not the official City of West Palm Beach website. Stable reference: corpuslaw.us/code/09f2ec86-f755-49c5-939a-ae86fa02375f

Sec. 38-43. - Size vents for flammable liquid tanks.

Each flammable liquid tank shall be vented through piping adequate in size to prevent blow-back of vapor or liquid at the fill opening while the tank is being filled. Minimum size of vents shall be in accordance with the following table: Minimum Requirements for Vent Size Capacity of Tanks Gallons | Diameter of Vent 0 to 500 | 1¼ inches 501 to 3,000 | 1½ inches 3,001 to 10,000 | 2 inches 10,001 to 25,000 | 2½ inches 25,001 to 50,000 | 3 inches 50,001 to 100,000 | 3½ inches 100,001 to 150,000 | 4 inches 150,001 to 400,000 | 5 inches 400,001 to 1,000,000 | 6 inches

(Ord. No. 3707-03, § 6, 11-24-2003)