Sec. 22-191. - Local limits.
The following pollutant limits are based on treatment plant design specifications and are established to protect against pass through and interference. User discharge concentrations apply at the point where the industrial waste is discharged to the sewage works. No person shall discharge wastewater containing in excess of the following maximum allowable discharge limits: Maximum Daily Concentrations (mg/l, 24-hour composite) Pollutant | User Discharge Ammonia | 555.7 Arsenic | 13.01 Five-day Biological Oxygen Demand (BOD) | 150 Cadmium | 0.62 Chromium | 0.56 Copper | 6.66 Cyanide | 1.82 Lead | 3.27 Mercury | 0.57 Molybdenum | 0.72 Nickel | 6.16 Oil & Grease | 100 PCB | 0 Phenol | 4.00 Selenium | 2.62 Silver | 4.73 Sulfate | 1500 Total Suspended Solids (TSS) | 200 Zinc | 10.62 The concentration limitations above are based on a specific mass limitation for each pollutant. The director may impose mass limitations in addition to, or in place of, the concentration limitations above. The city reserves the right to establish, by ordinance or in wastewater discharge permits, more stringent standards or requirements on discharges to the sewage works.
(Ord. No. 96-7-2, 7-22-96; Ord. No. 2022-5-2, § 1, 5-9-22)