§ 16-14.7 Standby electrical system capability.
(a) Provide a standby emergency electrical power system per International Building Code Chapter 27 and NFPA 70 Article 700 Emergency Systems and Article 701 Legally Required Standby Systems that has the capability of being connected to an emergency generator or other temporary power source. The emergency system capabilities must include: (1) An emergency lighting system; (2) Illuminated exit signs; (3) Fire protection systems, fire alarm systems, and fire sprinkler systems; and (4) Minimum mechanical ventilation for health/safety purposes. (b) Emergency generator. When emergency generators are pre-installed, the facility housing the generator, permanent or portable, must be an enclosed area designed to protect the generators from wind and missile impact. Generators hardened by the manufacturer to withstand the area’s design wind and missile impact criteria must be exempt from the enclosed area criteria requirement. (1990 Code, Ch. 16, Art. 14, § 16-14.6) (Added by Ord. 12-34; Am. Ord. 24-15)