29.41 - 307.2 Guards.
Section 307.2 of the IPMC is hereby amended by deleting said section and replacing it with the following: Guards shall be provided along open-sided walking surfaces, including balconies, porches, decks, stairs, ramps and landings, that are more than 30 inches (762 mm) above the floor or grade below. Exception: Guards shall not be required where exempted by the adopted building code. 307.2.1 Height. Guards shall be not less than 30 inches (762 mm) high. 307.2.2 Opening Limitations. Required guards shall not have openings from the walking surface to the required guard height that allow passage of a sphere 4 inches (102 mm) in diameter. Exceptions: 1. The triangular openings at the open side of stair, formed by the riser, tread and bottom rail of a guard, shall not allow passage of a sphere 6 inches (153 mm) in diameter. 2. Guards on the open side of stairs shall not have openings that allow passage of a sphere 4 3/8 inches (111 mm) in diameter. The new installation or replacement of handrails or guards require compliance with current Cedar Rapids Municipal Building Code. (033-24)