Sec. 26-216. - Duct leakage (prescriptive).

Delete section R403.3.4 and insert in lieu thereof the following new section: R403.3.4 Duct Leakage (Prescriptive). The total leakage of the ducts, where measured in accordance with Section R403.3.3 shall be as follows: (1) Rough-in test: Total leakage shall be less than or equal to 6 cfm (170 L/min) per 100 square feet (9.29 m2) of conditioned floor area where the air handler is installed at the time of the test. If the air handler is not installed at the time of the test, total leakage shall be less than or equal to 3 cfm (85 L/min) per 100 square feet (9.29 m2) of conditioned floor area. (2) Postconstruction test: Leakage to outdoors shall be less than or equal to 4 cfm (113.3 L/min) per 100 square feet (9.29 m2) of conditioned floor area or total leakage shall be less than or equal to 6 cfm (170 L/min) per 100 square feet (9.29 m2) of conditioned floor.