For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 46-521 — Access

Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 46-521

Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/a8233840-840d-4a35-bae1-88b3c8096188

Sec. 46-521. - Access.

Insert new section 3307.1.4 with the following language: Section 3307.1.4 Construction Site Access. Approved fire apparatus access roads shall be provided for every facility, building, or portion of a building as soon as construction commences. The fire apparatus access road shall comply with the requirements of section 503.2 and this section and shall extend to within 100 feet (30,480 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 100 feet (30,480 mm) where: (1) The building is equipped throughout with an approved automatic sprinkler system that is fully functional and installed in accordance with section 903.3.1.1, 903.3.1.2, or 903.3.1.3. (2) Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided.

(O.15,546, 16,318, 16,521)

Ask a question about Des Moines law

Corpus searches the Des Moines sections it holds and shows the ones that match, with their citations. Free, no sign-in.