For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 46-560 — Liquefied petroleum gas (LP-gas)

Municipal Code of the City of Des Moines, Iowa (Supp. No. 38, Update 3: codified through Ordinance No. 16,577, adopted August 24, 2026) · Des Moines Municipal Code § 46-560

Corpus is an independent public-information project, not the official City of Des Moines website. Stable reference: corpuslaw.us/code/95274e92-d0ca-48f0-b9bc-0010fb248201

Sec. 46-560. - Liquefied petroleum gas (LP-gas).

LP-gas shall be in accordance with chapter 41 and chapter 61 of the International Fire Code and NFPA 58. (1) LP-gas cylinder hoses. Hoses shall be designed for a working pressure of 350 psig (2413 kPa) with a safety factor of 5 to 1 and shall be continuously marked with LP-GAS, PROPANE, 350 PSI WORKING PRESSURE, and the manufacturer's name or trademark. Hose assemblies, after the application of couplings, shall have a design capability of 700 psig (4826 kPa). Hose assemblies shall be leak tested at the time of installation at not less the operating pressure of the system in which they are installed.

(O.15,546, 16,318, 16,521)