§ 50-3 — Performance Standards
Code of Ordinances, City of Aurora, Illinois; partial · Aurora Code of Ordinances § 50-3
Corpus is an independent public-information project, not the official City of Aurora website. Stable reference: corpuslaw.us/code/eaf782bc-724d-4666-93c0-3547be8f4715
Sec 50-3 Performance Standards
(a) All Data Center Facilities developed after March 25, 2026, must meet the standards in Section 49-104.3(c)(25) of the Aurora Zoning Ordinance. (b) All generators providing back-up power for Data Center Facilities developed after March 25, 2026, must meet the requirements outlined in 49-104.3(c)(25)(c) of the Aurora Zoning Ordinance. Unless the generators are supplying backup electrical supply during a power outage, testing of generators, regardless of whether installed before or after March 25, 2026, may only occur between the hours of 9:00 am and 5:00 pm Monday through Friday, and not on holidays. No more than two (2) generators may be tested simultaneously. (c) Any replacement equipment, including but not limited to generators, chillers, and screening, must meet the standards in Sec 49-104.3(c)(25) of the Aurora Zoning Ordinance for any Data Center Facilities developed after March 25, 2026. (d) For purposes of this Sec 50-3, "developed" means Data Center Facilities which do not have zoning entitlements pursuant to Chapter 49 of this Code as of March 25, 2026.
HISTORY Adopted by Ord. O26-021 on 3/24/2026