Sec. 22-604.2. - Service.

(a) The dwelling size and usage of electrical appliances and equipment shall serve as a basis for determining the need for additional facilities in accordance with the National Electrical Code (NEC), as adopted. (b) Every dwelling unit shall have the total connected load served by a single 120/240 volt or 208/120 volt set of 3-wire service or feeder conductors with an ampacity of not less than sixty (60) amperes with a separate meter. Minimum service and circuit load requirements shall be calculated in accordance with applicable existing dwelling sections of the National Electrical Code, as adopted. (c) Branch circuits required for the purpose of lighting, central alarm, signal, communications, or other needs for public or common areas of a two-family dwelling, a multifamily dwelling, or a multi-occupancy building shall not be supplied from equipment that supplies an individual dwelling unit or tenant space.

(C.B. No. 2016-115, § 1(Exh. 1), 6-6-16)