§ 14B-10-1020 — Corridors

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14B-10-1020

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/3f5f700e-5c6c-413a-8297-e90118585f8b

14B-10-1020 Corridors.

The provisions of Section 1020 of IBC are adopted by reference with the following modifications: 1. Delete exception 1 to Section 1020.1. 2. Replace Table 1020.1 as shown: TABLE 1020.1 CORRIDOR FIRE-RESISTANCE RATING OCCUPANCY | OCCUPANT LOAD SERVED BY CORRIDOR | REQUIRED FIRE-RESISTANCE RATING (hours) Without sprinkler system | With sprinkler system OCCUPANCY | OCCUPANT LOAD SERVED BY CORRIDOR | REQUIRED FIRE-RESISTANCE RATING (hours) Without sprinkler system | With sprinkler system H-1, H-2, H-3 | All | Not Permitted | 1 H-4, H-5 | Greater than 30 | Not Permitted | 1 A, B, F, M, S, U | Greater than 30 | 1 | 0 e E | All | 1 | 1 R | Greater than 10 | 1 | 1 I-2 a | All | Not Permitted | 0 I-1, I-3 | All | Not Permitted | 1 b I-4 | All | 1 | 0 a. For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3. b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8. c. [Reserved.] d. [Reserved.] e. In Groups A-1, A-2, A-3, and A-4 occupancies, corridors serving and visually separated from a room or suite of rooms with an occupant load of 300 or more shall have a fire-resistance rating of not less than 1 hour. 2.1. Revise Section 1020.1.1 by replacing "Section 3006.2.1" with "Section 3002.1.1." 3. Replace Table 1020.2 as shown: TABLE 1020.2 MINIMUM CORRIDOR WIDTH OCCUPANCY | MINIMUM WIDTH (inches) OCCUPANCY | MINIMUM WIDTH (inches) Any facility not listed in this table | 44 Access to and utilization of mechanical, plumbing or electrical systems or equipment | 24 With an occupant load of less than 50 | 36 Within or serving a single dwelling unit | 36 In Group E-1 corridors serving classrooms, study rooms or assembly rooms | 60 a In corridors and areas serving stretcher traffic in ambulatory care facilities | 72 Group I-2 in areas where required for bed movement | 96 For SI: 1 inch = 25.4 mm. a. When lockers are installed in corridors, the full required clear width of the corridor shall be provided between locker doors when open. 4. Revise exception 2 to Section 1020.4 to read: "2. In occupancies in Groups B, E-2, F, I-1, M, R, S and U, where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the length of the dead-end corridors shall not exceed 50 feet (15 240 mm)." 5. Revise Section 1020.5 including its exceptions to read: “1020.5 Air movement in corridors. Air movement in corridors shall comply with Section 601.2 of the Chicago Mechanical Code.” 6. [Reserved.] 7. Delete Section 1020.5.1. 8. Add a new Section 1020.7 to read: "1020.7 Toilet rooms. Separation shall not be required between a toilet room and a fire-resistance-rated corridor where the toilet room meets the following criteria: 1. The toilet room shall be separated from the remainder of the building by fire-resistance-rated construction meeting the requirements of Section 1020.1. 2. The toilet room shall not directly connect to any habitable space. 3. The toilet room shall not contain any fuel-fired equipment or appliances." (Amend Coun. J. 2-19-20, p. 14473, Art. II, § 49; Amend Coun. J. 10-7-20, p. 21791, Art. II, § 24; Amend Coun. J. 1-24-24, p. 8634, Art. IV, § 4; Amend Coun. J. 6-17-26, p. 45214, Art. IV, § 33)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.