§ 14B-14-1407 — Exterior insulation and finish systems (EIFS)
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14B-14-1407
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/ac92c02c-b0cd-4fb9-a1b0-de13844e8a97
14B-14-1407 Exterior insulation and finish systems (EIFS).
The provisions of Section 1407 of IBC are adopted by reference with the following modifications: 1. Revise Section 1407.4.1 and its subsections to read: "1407.4.1 Drainage. EIFS without drainage (barrier-type) shall not be permitted. EIFS shall have an average minimum drainage efficiency of 90 percent when tested in accordance with the requirements of ASTM E2273. Details of the required drainage mechanisms shall be provided on the construction documents. 1407.4.1.1 Water-resistive barrier. The water-resistive barrier shall comply with Section 1403.2 or ASTM E2570." 2. Revise Section 1407.5 to read: "1407.5 Installation. Installation of the EIFS shall be in accordance with the manufacturer’s instructions." 3. Delete Section 1407.6. (Amend Coun. J. 2-19-20, p. 14473, Art. II, § 64; Amend Coun. J. 6-25-21, p. 32180, Art. II, § 23)