For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 14B-7-713 — Shaft enclosures

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14B-7-713

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/42f43c19-25ed-40fb-87cf-01976a24eb37

14B-7-713 Shaft enclosures.

The provisions of Section 713 of IBC are adopted by reference with the following modifications: 1. Add a new exception to Section 713.4 to read: "Exception: Where shafts contain only noncombustible pipes, noncombustible conduit or iron, steel or aluminum ducts requiring floor penetrations not exceeding 9 square feet (0.8 m2) per story, the shaft enclosures connecting any number of stories shall have a fire-resistance rating of not less than 1 hour." 2. Revise section 713.11, including the exception, by deleting "approved." 3. Revise the second sentence of Section 713.13.1 to read: "A single shaft enclosure shall be permitted to contain recycling and waste chutes." 4. Revise the first sentence of Section 713.13.4 to read: "Waste or linen chutes shall discharge into an enclosed room separated by fire barriers with a fire-resistance rating not less than 2 hours and constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both." 5. Revise Section 713.13.6 by deleting "approved."

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.