§ 14X-5-505.12.6 — Access

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14X-5-505.12.6

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/52ef38e6-b512-4669-b23e-e785184042b1

14X-5-505.12.6 Access.

Access to a fire escape from a corridor may not require travel through an intervening room. Access to a fire escape stairway must be from a door or window providing a clear opening at least 30 inches (762 mm) wide and 36 inches (152 mm) high. Access to a fire escape stairway must be directly to a landing. The landing may not be higher than the floor or window sill level and may not be lower than 8 inches (203 mm) below the floor level or 24 inches (610 mm) below the window sill. (Amend Coun. J. 2-19-20, p. 14473, Art. V, § 32; Amend Coun. J. 10-7-20, p. 21791, Art. V, § 13)