For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 14X-8-803.4 — Large residential buildings

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 14X-8-803.4

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/aceb57c6-cd7e-482f-88bb-6afe1cbc2539

14X-8-803.4 Large residential buildings.

Buildings of Group R (residential) occupancy that contain more than 100 dwelling units or sleeping units or that are high-rise buildings must be provided with permanent cooling and dehumidification equipment capable of maintaining a room temperature of 75ºF (24ºC) and 50 percent relative humidity in at least one indoor common gathering space when the outdoor temperature is 92ºF (33ºC) and the mean coincident wet bulb temperature is 74ºF (23ºC). Exception: Prior to May 1, 2024, portable equipment may be used to meet this requirement. (Added Coun. J. 6-22-22, p. 49372, § 7)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.