18-28-1004.1 Standards.

Boilers shall be designed, constructed and certified in accordance with the ASME Boiler and Pressure Vessel Code, Section I or IV. Controls and safety devices for boilers with fuel input ratings of less than 12,500,000 Btu/hr (3,662,500 W) shall meet the requirements of ASME CSD-1. Controls and safety devices for boilers with inputs greater than or equal to 12,500,000 Btu/hr (3,662,500 W) shall meet the requirements of NFPA 85. Packaged oil-fired boilers and their control systems shall be listed and labeled in accordance with UL 726. Packaged electric boilers and their control systems shall be listed and labeled in accordance with UL 834. Solid-fuel-fired boilers shall be listed and labeled in accordance with UL 2523. Boiler external piping falls within the jurisdiction of the ASME Code and shall be ASME Code certified. (Amend Coun. J. 9-14-21, p. 35949, Art. X, § 4)