§ 18-28-1202.4 — Piping materials standards
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1202.4
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/02a44db2-9fcb-40ef-8a2b-f3ac11b0005f
18-28-1202.4 Piping materials standards.
Hydronic pipe shall conform to the standards listed in Table 18-28-1202.4. The exterior of the pipe shall be protected from corrosion and degradation. Table 18-28-1202.4 Hydronic Pipe Material | Standard (see Chapter 16) Material | Standard (see Chapter 16) Acrylonirile butadiene styrene (ABS) plastic pipe | ASTM D 1527; ASTM D 2282 Brass pipe | ASTM B 43 Brass tubing | ASTM B 135 Copper or copper- alloy pipe | ASTM B 42; ASTM B 302 Copper or copper- alloy tube (Type K, L, or M) | ASTM B 75; ASTM B 88; ASTM B 251 Chlorinated polyvinyl chloride (CPVC) plastic pipe | ASTM D 2846; ASTM F 441; ASTM F 442 Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pressure pipe | CSA CAN/CSA-B-137.10 Cross-linked polyethlene (PEX) tubing | ASTM F 876; ASTM F 877 Lead pipe | FS WW-P 325B Polybutylene (PB) plastic pipe and tubing | ASTM D 3309 Polyvinyl chloride (PVC) plastic pipe | ASTM D 1785; ASTM D 2241 Steel pipe | ASTM A 53; ASTM A 106 Steel tubing | ASTM A 254
Ask a question about Chicago law
Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.