§ 18-28-1305.1 — Size

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1305.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/0d530d9f-91e1-4285-9c3e-7597c641ed5d

18-28-1305.1 Size.

The fuel oil system shall be sized for the maximum capacity of fuel oil required. The minimum size of a supply line shall be 3/8-inch (9.5 mm) inside diameter nominal pipe or 3/8-inch (9.5 mm) OD tubing. The minimum size of a return line shall be 1/4 inch (64 mm) inside diameter nominal pipe or 5/16-inch (7.9 mm) outside diameter tubing. Copper tubing shall have 0.035-inch (0.9 mm) nominal and 0.032-inch (0.8 mm) minimum wall thickness.