§ 18-28-510.8.2 — Clearance to combustibles
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-510.8.2
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/60064cbb-9d69-4145-9228-d305cb363a5d
18-28-510.8.2 Clearance to combustibles.
Ducts shall have a clearance to combustibles in accordance with Table 18-28-510.8.2. Exhaust gases having temperatures in excess of 600°F (316°C) shall be exhausted to a chimney in accordance with Section 18-28-511.2. Table 18-28-510.8.2 Clearance to Combustibles Type of Exhaust or Temperature of Exhaust (°F) | Clearance to Combustibles (Inches) Less than 100 | 1 100 – 600 | 12 Flammable vapors | 6 For SI: 1 inch = 25.4 MM; °C = [(°F) - 32]/1.8. (Amend Coun. J. 11-8-12, p. 38872, § 320)