§ 18-29-504.6 — Relief valve approval

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-504.6

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/db080cac-e371-4500-9cf0-250603cd5f07

18-29-504.6 Relief valve approval.

Temperature and pressure relief valves (or combinations thereof) and energy cutoff devices shall bear the label of an approved agency and shall have a temperature setting of not more than 210°F (99°C) and a pressure setting not exceeding the tank or water heater manufacturer’s rated working pressure or 150 psi (1035 kPa), whichever is less. The relieving capacity of each pressure relief valve and each temperature relief valve shall equal or exceed the heat input to the water heater or storage tank. (Amend Coun. J. 6-17-26, p. 45214, Art. IV, § 54)