§ 5-1D-8 — AMENDMENTS TO FIRE CODE:

Municipal Code of Naperville, Illinois (Supp. No. 101: codified through Ordinance No. 26-049, adopted May 19, 2026) · Naperville Municipal Code § 5-1D-8

Corpus is an independent public-information project, not the official City of Naperville website. Stable reference: corpuslaw.us/code/6a05566e-92ec-465f-aa20-9136a11a6fbc

5-1D-8: - AMENDMENTS TO FIRE CODE:

The various sections of the IFC, 2024 edition, are hereby revised as follows: Section 110.4 Violation Penalties: Change to read: Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the building official, or of a permit or certificate issued under the provisions of this code, shall be subject to penalties as prescribed by law and/or in Section 5-1A-3 (Amendments): Section 109.4 (Work Commencing Without a Permit) of this Title. Section 308.1.4 Open-Flame Cooking Devices: Add the following exceptions: 4. When an open-flame cooking device is attended by an adult and a minimum 10 lb. dry chemical (class B or class ABC) fire extinguisher is located within ten (10) feet of the cooking device. 5. When an LP gas fueled cooking device is attended by an adult and a minimum 10 lb. dry chemical (class B or class ABC) fire extinguisher is located within ten (10) feet of the cooking device. Section 311.2.2 Fire Protection: Delete exceptions nos. 1, 2, and 3 Section 505.1 Address Numbers: Change to read: Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position on the building that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 5½" high with a minimum stroke width of 0.5 inch (12.7mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. All multi-tenant commercial buildings and multi-family residential dwelling units shall have additional address numbering placed on the rear door, if appropriate, with the same requirements noted above. Exception: detached residential garages. Address identification shall be maintained. Section 507.5.1 Fire Hydrant Systems: 507.5.1 Where Required: Change to read: Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the code official. Section 507.5.1 Where Required: Delete exceptions. Section 507.5.1.1: Hydrant for standpipe systems: Change to read: Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 50 feet of the fire department connections. Section 704 Floor Openings and Shafts: Add a new section as follows: 704.3 Existing Buildings: Existing buildings remodeled, altered, or additions to, existing fusible-link-type automatic door-closing devices are not permitted. Section 903 Automatic Sprinkler Systems: Change to read: Automatic sprinkler systems shall comply with the requirements of the International Building Code, as amended by city ordinances. Section 903.1 through 903.6:4- Delete in its entirety. Section 905.3 Required Installation: Delete the exception. Section 905.3.1 Height: Add as follows: Class III standpipe systems shall also be installed throughout buildings where the floor level of the highest story is 3 stories with 25 foot corridors in length and all buildings which are 4 stories in height, including penthouses. Section 907.2 Where Required: Change the first paragraph to read as follows: An approved manual, automatic, or manual and automatic fire alarm system installed in accordance with the provisions of the 2024 IBC as amended, NFPA 72, and the current edition of the Naperville Fire Department's Regulations for the installation, maintenance, and testing of fire alarm systems, as amended from time to time, shall be provided in new buildings and structures in accordance with Section 907.2.1 through Section 907.2.24, unless other requirements are provided by another section of this code. Where automatic sprinkler protection installed in accordance with IBC Section 903.3.1.1 connected to the building fire alarm system, automatic heat detection required by this section shall not be required. Section 907.2: Add the following subsections: Section 907.2.24: Fire alarm and detection systems for townhouses shall be installed in multiple single-family dwellings (townhouses), if the building or structure contains three (3) or more units. All fire alarm and detection systems shall be listed and installed in accordance with the provisions of NFPA 72, the IBC 2024, the IFC 2024, and the current edition of the Naperville Fire Department's Regulations for the installation, maintenance, and testing of fire alarm systems, as amended from time to time. Section 2306.2.3 Above-Ground Tanks Located Outside, Above Grade: Change #3 to read as follows: 3. Above-ground tanks containing fuels shall not exceed 2,000 gallons in individual capacity or 2,000 gallons in aggregate capacity. Installations with the maximum allowable aggregate capacity shall be separated from other such installations by not less than 100 feet (30 480 mm). Add the following: 6. Above-ground tanks shall not be used for the outside storage of motor fuels at automotive service stations and dispensing facilities. Section 2306.2.4.1. Tank Capacity Limits. Change to read as follows: Tanks storing class I and class II liquids at an individual site shall be limited to a maximum individual capacity of 2,000 gallons and an aggregate capacity of 2,000 gallons. Add the following: 1. Tank capacity limits special conditions. Tank capacities may be exceeded due to special conditions and must be approved by the chief building official and the district fire chief. 2. Fleet vehicle motor fuel-dispensing facilities. Change to read as follows: Tanks storing class II and class IIIA liquids at a fleet vehicle motor fuel-dispensing facility shall be limited to a maximum individual capacity of 2,000 gallons and an aggregate capacity of 2,000 gallons. Section 2306.2.6 Special Enclosures. Change #6 to read as follows: 6. Tanks containing class I, II, or IIIA liquids inside a special enclosure shall not exceed 2,000 gallons in individual capacity or 2,000 gallons in aggregate capacity. CHAPTER 1 BUILDING CODES

(Ord. No. 02-31, 2-19-2006, eff. 4-8-2002; Ord. No. 06-301, 12-19-2006, eff. 1-1-2007; Ord. No. 08-056, 3-18-2008; Ord. No. 12-159, § 1(Exh. A), 12-18-2012; Ord. No. 18-141, § 2, 12-4-2018; Ord. No. 26-010, § 2, 2-17-2026)

Ask a question about Naperville law

Corpus searches the Naperville sections it holds and shows the ones that match, with their citations. Free, no sign-in.