§ 8-2A-2 — CROSS CONNECTION REGULATIONS:

Municipal Code of Naperville, Illinois (Supp. No. 101: codified through Ordinance No. 26-049, adopted May 19, 2026) · Naperville Municipal Code § 8-2A-2

Corpus is an independent public-information project, not the official City of Naperville website. Stable reference: corpuslaw.us/code/81b11b2c-cbbf-4dd3-8ff4-757eac0ef199

8-2A-2: - CROSS CONNECTION REGULATIONS:

1. In the context of this Article, the following words and phrases shall have the meanings ascribed by this Subsection: AGENCY: | The Illinois Environmental Protection Agency. APPROVED: | Backflow prevention devices or methods approved by the research foundation for cross connection control of the University of Southern California, the American Water Works Association, American National Standards Institute, American society of sanitation engineers and certified by the national sanitation foundation. ATMOSPHERIC VACUUM BREAKER: | A backflow prevention device used as protection against cross connection where the device is not subjected to backpressure due to pumps or any other conditions which may cause backpressure. This device may never have a downstream shutoff valve, or be installed where it will be in continuous operation for more than twelve (12) hours. AUXILIARY WATER SYSTEM: | Any water source or system on or available to the premises other than the public water supply system and includes the water supplied by the system. These auxiliary waters may include water from another purveyor's public water supply system, water from a source such as wells, lakes or streams, process fluids, or used water. These waters may be polluted or contaminated or objectionable or constitute a water source or system over which the water purveyor does not have control. BACK SIPHONAGE: | The flowing back of used, contaminated or polluted water due to a negative gauge or subatmospheric pressure in that pipe. BACKFLOW: | The flow of any water, foreign liquids, gases or other substances back into the distribution pipes of the potable water system. BACKFLOW PREVENTION DEVICE: | Any device, method or type of construction intended to prevent backflow into a potable water system. All devices used for backflow prevention in Illinois must meet the standards of the plumbing codes and the Illinois Environmental Protection Agency. CONTAMINATION: | An impairment of the quality of the water by entrance of any substance to a degree which could create a health hazard. CROSS CONNECTION: | Any physical connection or arrangement between two (2) otherwise separate piping systems, one of which contains potable water and the other a substance of unknown or questionable safety or quality, whereby there may be a flow from one system into the other. 1.1. "Direct cross connection" means a cross connection formed when a water system is physically joined to a source of unknown or unsafe substance. 1.2. "Indirect cross connection" means a cross connection through which an unknown substance can be forced, drawn by vacuum or otherwise introduced into a safe potable water system. CROSS CONNECTION CONTROL DEVICE INSPECTOR OR CCCDI: | A plumber who holds an Illinois plumbing license issued in accordance with 225 Illinois Compiled Statutes 320/3(1), and who has successfully completed both the written and performance examinations offered by the Agency. These examinations demonstrate an understanding of the principles of backflow and back siphonage, and the hazard presented to a potable water system; identifying locations which require installation of cross connection control devices; identifying, locating, inspecting, testing, maintaining and repairing cross connection control methods and devices in line, as located throughout each system which connects to a community public water supply. These requirements are described in 35 Ill. Adm. Code 653.802(d)(1)(D) through (F). DEPARTMENT: | The Illinois Department of Public Health. DIRECTOR: | The Director of the City of Naperville Department of Public Utilities system or their designee. DOUBLE CHECK VALVE ASSEMBLY: | An assembly which is effective against backflow caused by backpressure and backsiphonage, which is used to protect the potable water system from pollutants that would not constitute an actual health hazard, but might be objectionable to the water supply system. The double check valve assembly is used to isolate nonhealth hazards. DOUBLE CHECK DETECTOR ASSEMBLY: | An assembly designed to prevent contamination of the potable water system by backflow from the fire protection system containing nontoxic substances. DRAIN: | Any pipe that carries wastewater or water-borne wastes in a building drainage system. FIXED PROPERTY AIR GAP: | The unobstructed vertical distance through the free atmosphere between the water discharge point and the flood level rim of the receptacle. HEALTH HAZARD: | Any condition, device or practice in a water system or its operation resulting from a real or potential danger to the health and well-being of consumers. The word "severe" as used to qualify "health hazard" means a hazard to the health of the user that could be expected to result in death or significant reduction in the qualify of life. INSPECTION: | A plumbing inspection to examine carefully and critically all materials, fixtures, piping and appurtenances, appliances and installations of a plumbing system for compliance with requirements of the Illinois Plumbing Code, 77 Ill. Adm. Code 890. NONPOTABLE WATER: | Water not safe for drinking, personal or culinary use as determined by the requirements of 35 Ill. Adm. Code. 604. PLUMBING: | The actual installation, repair, maintenance, alteration or extension of a plumbing system by any person. Plumbing includes all piping, fixtures, appurtenances and appliances for a supply of water for all purposes, including without limitation, lawn sprinkler systems, from the source of private water supply on the premises or from the main in the street, alley or at the curb to, within and about any building or buildings where a person or persons live, work or assemble. Plumbing includes all piping, from discharge of pumping units to and including pressure tanks in water supply systems. Plumbing includes all piping, fixtures, appurtenances and appliances for a building or buildings where a person or persons live, work or assemble from the point of connection of such building drain to the building sewer or private sewage disposal system five (5) feet beyond the foundation walls. POLLUTION: | The presence of any foreign substance (organic, inorganic radiological or biological) in water that tends to degrade its quality so as to constitute, reduce or impair the usefulness of the water. POTABLE WATER: | Water which meets the requirements of 35 Ill. Amd. Code 604 for drinking, culinary and domestic purposes. PROCESS FLUID(S): | Any fluid or solution which may be chemically, biologically or otherwise contaminated or polluted in a form or concentration such as would constitute a health, pollution or system hazard if introduced into the public or a consumer's potable water system. This includes but is not limited to: 1.1. Polluted or contaminated waters; 1.2. Process waters; 1.3. Used waters originating from the public water supply system which may have deteriorated in sanitary quality; 1.4. Cooling waters; 1.5. Questionable or contaminated natural waters taken from wells, lakes, streams or irrigation systems; 1.6. Chemicals in solution or suspension. 1.7. Oils, gases, acids, alkalis and other liquid and gaseous fluids used in industrial or other processes, or for firefighting purposes. PROPERTY OWNER or CUSTOMER: | The owner, tenant, occupant, official custodian or person in control of any premises supplied by or in any manner connected to a public water system. PROPERTY OWNER'S WATER SYSTEM: | Any water system located on the customer's premises. A building plumbing system is considered to be a customer's water system. PUBLIC WATER SUPPLY: | All mains, pipes and structures through which water is obtained and distributed to the public, including wells, and well structures, intakes, and cribs, pumping stations, treatment plants, reservoirs, storage tanks and appurtenances, collectively or severally, actually used or intended for use for the purpose of furnishing water for drinking or general domestic use and which serve at least fifteen (15) service connections or which regularly serve at least twenty-five (25) persons at least sixty (60) days per year. A public water supply is either a "community water supply" or a "noncommunity water supply". REDUCED PRESURE PRINCIPLE BACKFLOW PREVENTION DEVICE: | A device containing a minimum of two (2) independently acting check valves together with an automatically operated pressure differential relief valve located between the two (2) check valves and approved under ASSE standard 1013, USC manual for RPZ devices or AWWA C506. During normal flow and at the cessation of normal flow, the pressure between these two (2) checks shall be less than the supply pressure. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure between the check valves at less than the supply pressure. The unit must include tightly closing shut off valves located at each end of the device, and each device shall be fitted with properly located test cocks. SERVICE CONNECTION: | The opening, including all fittings and appurtenances, at the water main through which water is supplied to the user. SURVEY: | The collection of information pertaining to a customer's piping system regarding the location of all connections to the public water supply system and must include the location, type and most recent inspection and testing date of all cross connection control devices and methods located within that customer's piping system. The survey must be in written form, and should not be an actual plumbing inspection. SYSTEM HAZARD: | A condition through which an aesthetically objectionable or degrading material not dangerous to health may enter the public water supply system or a consumer's potable water system. USEPA: | The United States Environmental Protection Agency. USFDA: | The United States Food and Drug Administration. USED WATER: | Any water supplied by a public water supply system to a consumer's water system after it has passed through the service connection and is no longer under the control of the water supply official custodian. VACUUM: | Any pressure less than that exerted by the atmosphere. WATER PURVEYOR: | The owner or official custodian of a public water system. 2. The components of the City water system shall include the public water supply system and the property owner's water system. 2.1. The public water supply system shall consist of the water source facilities and the distribution system, and shall include all those facilities of the potable water system under the control of the Director up to the point where the property owner's water system begins. 2.2. The property owner's water system shall include all of the facilities beyond the customer's side of the property line service connection (curb stop/shut off) used to convey water from the public water supply distribution system to the customer's points of use. 3. Connections between potable water systems and other systems, devices or equipment containing water or other substances of unknown or questionable quality are prohibited except when and where approved cross connection control devices or methods are installed, tested and maintained to ensure proper operation on a continuing basis. 3.1. There shall be no facility, arrangement, device or connection by which an unsafe substance may enter a potable water supply. 3.2. All property owners shall prevent backflow into the public water system by ensuring that: 3.2.1. All cross connections are eliminated or approved cross connection control devices are installed by a CCCDI in accordance with the manufacture's specifications for control of backflow and back siphonage. 3.2.2. All cross connection control devices shall be inspected at least annually by a person approved by the Agency as a cross connection control device inspector (CCCDI). The inspection of mechanical devices shall include physical testing in accordance with the manufacturer's instructions and shall be at the property owner's expense. 4. This Section establishes an active cross connection survey, investigation and records control program which includes, without limitation: 4.1. A cross connection control survey of the distribution system shall be conducted by the Director at least every two (2) years. 4.1.1. The purpose of this survey is to compile and update an inventory of devices; 4.1.2. The survey shall consist of a pencil and paper collection of information, conducted by telephone, mail or personal visit to the owner, tenant, occupant or manager of a specific property. 4.2. All property owners' premises shall, upon reasonable notice and at reasonable times, be open to the Director for the inspection of the presence or absence of cross connections, testing, repair and maintenance of cross connection control devices within the property owner's premises. 4.3. All property owners shall arrange periodic surveys of water use practices on the premises to determine whether there are actual or potential cross-connections to the water system through which contaminants or pollutants could backflow into the private or public potable water system. These surveys shall be at the property owners' expense. 5. An approved backflow prevention device shall be installed on each service line to a property owner's water system, where, in the judgment of an Agency certified CCCDI, an actual or potential hazard to the public water supply system may exist, including without limitation: 5.1. Premises having an auxiliary water supply, unless such auxiliary supply is accepted as an additional source by the Director, and the source is approved by the Illinois Environmental Protection Agency; 5.2. Premises on which any substance is handled which can create an actual or potential hazard to the public water supply system, including without limitation, premises having sources or systems containing process fluids or waters originating from the public water supply system which are no longer under the Director's sanitary control; 5.3. Premises having internal plumbing connections that, in the Director's judgment, are too intricate to determine whether or not cross-connections exist; 5.4. Premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete cross-connection survey; and 5.5. Premises where cross-connections have been previously established or re-established. 6. Unless an Agency certified CCCDI determines that no actual or potential hazard to the public water supply system exists, an approved backflow prevention device shall be installed in accordance with the specifications of this Chapter on each service line to a property owner's water system serving, without limitation, facilities including: 6.1. Hospitals, mortuaries, clinics, nursing homes; 6.2. Laboratories; 6.3. Piers, docks and waterfront facilities; 6.4. Sewage treatment plants, sewage pumping stations or water pumping stations; 6.5. Food or beverage processing and/or dispensing equipment; 6.6. Chemical plants; 6.7. Metal plating industries; 6.8. Petroleum processing or storage plants; 6.9. Radioactive material processing plants or nuclear reactors; and 6.10. Car washes. 7. Based on the degree of hazard to the water system, an appropriate level of protection shall be required, including, without limitation: 7.1. An approved fixed proper air gap separation shall be installed where the public water supply system may be contaminated with substances that could cause a severe health hazard; 7.2. An approved fixed proper air gap separation or an approved reduced pressure principle backflow prevention device shall be installed where the public water supply system may be contaminated with a substance that could cause a system or health hazard. 7.3. An approved fixed proper air gap separation or an approved double detector check valve assembly backflow prevention device shall be installed where the public water supply system may be polluted with substances that could cause a pollution hazard not dangerous to health. 8. Fire safety systems shall be equipped with a double detector check valve assembly located at the point of connection between the fire safety system and the water supply line to protect the water supply against backflow and backsiphonage except under the conditions described in Subsection 8.1 below: 8.1. A fixed proper air gap with a break tank or other storage vessel or a reduced pressure principle backflow preventer shall be installed at the point of connection between the fire safety system and the water supply service line to protect the water supply against backflow and backsiphonage when: 8.1.1. The fire safety system contains additives such as antifreeze, fire retardant or other chemicals. The RPZ assembly may be located at the point of connection to the section of the system containing such additives when the connection to the water supply is protected by a double detector check valve assembly; or 8.1.2. Water is pumped into the fire safety system from a nonpotable source capable of serving the fire safety system. A nonpotable source of water shall be considered capable of serving the fire safety system under the following conditions: it must be capable of year-round use, maintained with not less than fifty thousand (50,000) gallons of usable water not subject to freezing, accessible to fire-fighting pumper equipment, located within one thousand seven hundred (1,700) feet of the facility; or 8.1.3. Water flows into the fire safety system by gravity from a nonpotable source; or 8.1.4. There is a permanent or emergency connection whereby water can be pumped into the fire safety system from any other nonpotable source. 8.2. Fire Department connections served solely by a water system without any nonpotable connections or chemical additives shall require installation of a double detector check valve assembly. 9. Only cross-connection control devices which are approved by the Research Foundation for Cross-Connection Control of the University of Southern California, the American Water Works Association, American Society of Sanitary Engineering and the American National Standards Institute and certified by the National Sanitation Foundation to be in compliance with applicable industry specifications shall meet the requirements of this Chapter. 9.1. Installation of approved devices shall be made only as specified by the Research Foundation for Cross-Connection Control of the University of Southern California, American Water Works Association, American Society of Sanitary Engineering, and the American National Standards Institute. 9.2. Maintenance as recommended by the manufacturer of the device shall be performed. The manufacturer's maintenance manual shall be available on the premises. 9.3. In addition to the requirements contained in this Section, only cross-connection control devices which meet the City Standard Specifications for Cross-Control Devices shall be approved for use. 10. Installation of approved devices shall be made in accordance with 35 Ill. Adm. Code 653.802, and only as specified by the Research Foundation for Cross-Connection Control of the University of Southern California or applicable industry specifications. 11. Maintenance as recommended by the manufacturer of the device shall be performed. Manufacturer's maintenance manual shall be available on-site. 12. Approved cross-connection control devices include: 12.1. A fixed proper air gap which shall be used whenever technically possible. 12.2. Atmospheric vacuum breakers which may be installed subject to the following conditions: 12.2.1. An atmospheric vacuum breaker shall not be installed where back pressure may occur; 12.2.2. An atmospheric vacuum breaker shall be installed at the highest point in the water line and after the last control valve before the point of discharge and a minimum of six (6) inches above the flood level rim of the receptacle; 12.2.3. An atmospheric vacuum breaker shall not be used for installations where the substance in the container receiving water is lethal or toxic. Examples of acceptable installations include, without limitation: 12.2.3.1. Surface wash piping for a gravity filter; 12.2.3.2. Solution tanks of gravimetric dry chemical feeders; 12.2.3.3. Outlets with hose attachments; and 12.2.3.4. Receptacles with a low level inlet where the substance contained is nontoxic such as food or beverages; 12.3. Reduced pressure principle backflow preventers (RPZ) may be installed in accordance with the specifications of this Chapter, subject to the following conditions: 12.3.1. Installation: 12.3.1.1. Units shall be accessible for maintenance and testing; 12.3.1.2. Minimum clearances recommended by the manufacturer shall be used; 12.3.1.3. Relief ports shall not be plugged. A drain of sufficient size to accommodate the RPZ water discharge rate of flow shall be provided and shall remain free flowing under all conditions; 12.3.1.4. A collection system with an air gap under the relief port drain shall be installed with ceiling level units; and 12.3.1.5. No reduction shall be made in the size of the relief port drain. 12.3.2. Bypasses: 12.3.2.1. A second backflow preventer shall be installed parallel to the first if there is only one service line and the water service cannot be interrupted. Bypass lines without approved backflow preventers shall not be installed. 12.3.3. Reduced Pressure Principle Backflow Preventers: 12.3.3.1. Reduced pressure principle backflow preventers shall be used for installations where a fixed proper air gap is not possible, including, without limitation: 12.3.3.1.1. The water line used to provide makeup water for chemical feeders in a water treatment plant; 12.3.3.1.2. Receptacles with a low level inlet where the contents are nontoxic such as food or beverages; and 12.3.3.1.3. Receptacles or vessels which can subject the water supply line to back pressure. 12.3.4.1. Water service lines which connect a community water supply to industrial or commercial establishments shall include either a reduced pressure principle backflow preventer or a fixed proper air gap with repumping if those establishments constitute a hazard to the water supply due to the nature of chemicals or other material handled within the facility. 13. Instantaneous water heaters and water storage heaters using shell and tube design hot water boiler-fired heat exchangers shall be acceptable for heating water for domestic use under the following conditions: 13.1. Chemical additives to control corrosion and scale of the hot water boiler system shall not contain toxic chemicals (e.g., chromate or nitrite based inhibitors). 13.1.1. Chemicals approved by the U.S.E.P.A. or U.S.F.D.A. which will not break down to harmful substances in the system may be applied for scale and corrosion control in public water supplies (e.g., food grade caustic soda, sodium silicate, sodium polyphosphate). 13.1.2. The addition of sodium sulfite as an oxygen scavenger in hot water boilers is acceptable when approved double check-valves in compliance with 35 Ill. Adm. Code §653.801(d) are installed. 13.2. A double check-valve assembly, in compliance with 35 Ill. Adm. Code §653.801(d) of the Illinois Administrative Code shall be installed in the cold water inlet piping of the heat exchanger. 13.2.1. The unit shall be tested annually and required service performed within fifteen (15) days; and 13.2.2. A maintenance log shall be maintained and include information specified in 35 Ill. Adm. Code §653.802(e)(4). 14. The property owner, tenant or occupant of any premises where backflow prevention devices required by this Section are installed shall have all such devices inspected, tested, maintained and repaired in accordance with the following schedule or more often where inspections indicate a need or are specified in manufacturer's instructions. All such inspections, maintenance, repairs and replacement costs shall be the sole expense of the property owner. 14.1. Fixed proper air gap separations shall be inspected at the time of installation and at least annually thereafter. 14.2. Double check valve assemblies shall be inspected and tested at the time of installation and at least annually thereafter, and any required services shall be performed within fifteen (15) days. 14.3. Reduced pressure principle backflow prevention devices shall be tested upon installation and at least annually or more frequently if recommended by the manufacturer. Any required service shall be performed within five (5) days. 15. Testing shall be performed by a CCCDI certified by the Agency as competent to service the device. Proof of the CCCDIs certification shall be in writing and filed with the City prior to testing. 16. Each device shall have a legible tag attached listing the date of most recent test or visual inspection, name of tester, and type and date of repairs. 17. A maintenance log shall be maintained and include: 17.1. The date of each test or visual inspection; 17.2. The name and approval number of person performing the test or visual inspection; 17.3. The test results; 17.4. The repairs or servicing required; 17.5. The repairs and date completed; and 17.6. The service performed and date completed. 18. Backflow prevention devices shall not be bypassed, made inoperative, removed or otherwise made ineffective without the Director's specific authorization. 19. Where a booster pump has been installed on the service line to or within any premises, such pump shall be equipped with a low pressure cut-off device designed to shutoff the booster pump when the pressure in the service line on the suction side of the pump drops to twenty (20) psi or less. 19.1. The property owner, the tenant or the occupant shall maintain the low pressure cut-off device in proper working order and shall certify to the Director, at least once a year, that the device is operable. 20. Violations of this Section: 20.1. The Director shall notify the owner, tenant or occupant of a building or premises where a violation of this Section is determined to exist. 20.2. The Director shall set a reasonable time, based on the level of hazard to health, for the owner, tenant or occupant to have the violation removed or corrected. 20.3. Upon the failure of the property owner, tenant or occupant to have the defect corrected by the end of the specified time period, the Director may pursuant to the notice provisions of Chapter 3 of this Title, order water service to the building or premises to be disconnected. 20.4. Water service shall not be reinstated until all violations of this Section have been removed or corrected and fees for reinstatement of service pursuant to Chapter 3 of this Title have been paid to the Finance Department. 20.5. The property owner, tenant or occupant of any property or premises who knowingly permits a violation to remain in place and/or uncorrected after the expiration of time set by the Director shall, upon conviction by a court of competent jurisdiction, be required to pay a fine of not less than five hundred dollars ($500.00). Each day a violation continues to exist uncorrected shall be considered to be a separate offense. 21. Appeals under this Section. 21.1. Any property owner, tenant, occupant or property manager (hereinafter the petitioner) may request a hearing before the Director within seven (7) days from the date of any notice of termination for a violation of the regulations of this Section. 21.2. The hearing date shall be scheduled during regular City business hours at the convenience of the parties, but no later than ten (10) days from the date of the request. 21.3. The hearing date and time shall be confirmed by the Director in writing to the petitioner by first class U.S. mail. 21.4. At such a hearing, the petitioner shall have the right to be represented by counsel, to appear at the hearing in person, to present evidence in his own behalf and to examine any evidence which the Director might introduce. 21.5. The Director shall conduct his own investigation of the petitioner's complaint and present any evidence to that effect at the hearing. 21.6. Within five (5) days after the conclusion of any hearing, the Director or his selected hearing officer shall render a decision on the basis of the evidence presented. Such decision shall be communicated to the petitioner by certified mail, return receipt required, by personal delivery, or by posting the premises to be disconnected from service. 21.7. Where the hearing officer's decision is against the petitioner, the notice of the decision shall specify that if the violation is not corrected, on or before five (5) days from the date of receipt of the notice, the water service shall be discontinued.

(Ord. No. 92-234, 12-15-1992; amd. Ord. No. 02-31, 2-19-2002, eff. 4-8-2002; Ord. No. 22-044, § 2, 5-3-2022) (Ord. No. 93-179, 9-21-1993) (Ord. No. 92-234, 12-15-1992) (Ord. 93-179, 9-21-93) (Ord. 92-234, 12-15-92)

Ask a question about Naperville law

Corpus searches the Naperville sections it holds and shows the ones that match, with their citations. Free, no sign-in.