§ 52.16 — General technical requirements
Code of Ordinances, City of Springfield, Illinois (Supp. No. 82: codified through Ordinance No. 146-04-26, enacted April 7, 2026) · Springfield, Ill., City Code § 52.16
Corpus is an independent public-information project, not the official City of Springfield website. Stable reference: corpuslaw.us/code/c143d1ba-0224-41ed-aff2-309b2d366d78
§ 52.16. - General technical requirements.
(a) A potable water supply system shall be designed, installed, and maintained in such manner as to prevent contamination from nonpotable liquids, solids, or gases from being introduced into the potable water supply through cross-connections or any other piping connections to the system. (b) Cross-connections between potable water systems and other systems or equipment containing water or other substances of unknown or questionable safety are prohibited except when and where, as approved by the water division, and in conformance with the Illinois State Plumbing Code, suitable protective devices such as the reduced pressure zone backflow preventer or equal are installed, tested, and maintained to ensure proper operation on a continuing basis. (c) Interconnection between two or more public water supplies shall be permitted only with the approval of the water division. (d) Cross-connections between an individual water supply and a potable public supply shall not be made unless specifically approved by the water division. (e) Potable water connections to boilers shall be made through an airgap or provided with an approved backflow preventer. (f) Connection to the potable water supply system for the following is prohibited unless protected against backflow in accordance with subsection (h) or as set out herein. (1) Bidets. (2) Operating, dissection, embalming, and mortuary tables or similar equipment, in such installation the hose used for water supply shall terminate at least 12 inches away from every point of the table or attachments. (3) Pumps for nonpotable water, chemicals, or other substances, priming connections may be made only through an airgap. (4) Building drainage, sewer, or vent systems. (5) Any other fixture or similar hazard. (g) Except where potable water provided for a refrigerator condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant, the inlet connection shall be provided with an approved check valve arrangement. Also adjacent to and at the outlet side of the check valve arrangement an approved pressure relief valve set to relieve at five psi above the maximum water pressure at a point of installation shall be provided if the refrigeration units contain more than 20 pounds of refrigerants. (h) Protection against backflow and backsiphonage. (1) A potable water system shall be protected against backflow and backsiphonage by providing and maintaining at each outlet: a. An airgap, as specified in subsection (h)(2) below, between the potable water outlet and the flood level rim of the fixture it supplies or between the outlet and any other source of contamination. b. A device or means to prevent backflow. (2) Minimum required airgap. a. The minimum required airgap shall be measured vertically from the lowest end of a potable water outlet to the flood rim or line of the fixture or receptacle into which it discharges. b. The minimum required airgap shall be twice the effective opening of a potable water outlet unless the outlet is a distance less than three times the effective opening away from a wall or similar vertical surface, in which cases the minimum required airgap shall be three times the effective opening of the outlet. In no case shall the minimum required airgap be less than shown in subsection (h)(3) below. (3) Minimum airgaps for generally used plumbing fixtures. Fixture | Minimum Airgap When Not Affected Near Wall (inches) a | When Affected by Near Wall (inches);sup\sup; Lavatories and other fixtures with effective openings not greater than ½-inch diameter. | 1.0 | 1.5 Sinks, laundry trays, gooseneck bath faucets, and other fixtures with effective openings not greater than ¾-inch diameter | 1.5 | 2.25 Over rim bath fillers and other fixtures with effective openings not greater than one inch diameter. | 2.0 | 3.0 Drinking water fountains, single orifice 0.437-inch diameter or multiple orifices having total area of 0.150 square inch (area of circle 7/16 -inch diameter). | 1.0 | 1.5 Effective openings greater than one inch. | 3 times diameter of effective opening | 2 times diameter of effective opening a. Side walls, ribs, or similar obstructions do not affect airgaps when spaced from inside edge of spout opening a distance greater than three times the diameter of the effective opening for two intersecting walls. b. Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening require a greater airgap when spaced closer to the nearest inside edge of spout opening than specified in note a above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the airgap shall be measured from the top of the wall. (4) Before any device for the prevention of backflow or backsiphonage is installed, it shall have first been certified by a recognized testing laboratory acceptable to the agency general superintendent. Devices installed in a building potable water supply distribution system for protection against backflow shall be maintained in good working condition as provided for in section 52.17, by the person or persons responsible for the maintenance of the system. (5) Installation of devices. a. Vacuum breakers shall be installed with the critical level at least six inches above the floodlevel rim of the fixture they serve and on the discharge side of the last control valve to the fixture. No shutoff valve or faucet shall be installed beyond the vacuum breaker. For closed equipment or vessels such as pressure sterilizers, the top of the vessel shall be treated as the floodlevel rim but a check valve shall be installed on the discharge side of the vacuum breaker. b. A reduced pressure principle type backflow preventer when approved may be installed subject to full static pressure. c. Backflow and backsiphonage preventing devices shall be accessibly located preferably in the same room with the fixture they serve. Installation in utility or service spaces, provided they are readily accessible, is also permitted. (6) Where potable water outlet terminates below the rim of a tank or vat and the tank or vat has an overflow of diameter not less than given in subsection (h)(7), the overflow pipe shall be provided with an airgap as close to the tank as possible. (7) Sizes of overflow pipes for water supply tanks. a. Maximum Capacity of Water Supply Line to Tank | Diameter of Overflow Pipe (inches ID) 0 to 50 gpm | 2 50 to 150 gpm | 2½ 100 to 200 gpm | 3 200 to 400 gpm | 4 400 to 700 gpm | 5 700 to 1000 gpm | 6 Over 1000 gpm | 8 b. The potable water outlet to the tank or vat shall terminate a distance not less than 1½ times the height to which water can rise in the tank above the top of the overflow. This level shall be established at the maximum flow rate of the supply to the tank or vat and with all outlets except the airgap overflow outlet closed. c. The distance from the outlet to the high water level shall be measured from the critical point of the potable water supply outlet. (8) a. Approved devices to protect against backflow and backsiphonage shall be installed at all fixtures and equipment where backflow or backsiphonage may occur and where a minimum airgap cannot be provided between the water outlet to the fixture or equipment and its floodlevel rim. b. Where a water connection is not subject to backpressure, a vacuum breaker shall be installed on the discharge side of the last valve on the line serving the fixture or equipment. A list of some conditions requiring protective devices of this kind is given in subsection (h)(9). (9) Cross-connections where protective devices are required and critical level (C-L) settings for vacuum breakers. a. Fixture or Equipment | Method of Installation Aspirators and ejectors. | C-L at least six inches above flood level of receptacle served. Dental units, on models with built-in vacuum breakers | C-L at least six inches from flood level rim of bowl. Dishwashing machines. | C-L at least six inches above flood level of machine. Install on both hot and cold water supply line. Flushometers (closet and urinal). | C-L at least six inches above top of fixture supplies. Garbage can cleaning machines. | C-L at least six inches above flood level of machine. Install on both hot and cold water supply lines. Hose outlets. | C-L at least six inches above highest point on hose line. Laundry machines. | C-L at least six inches above flood level of machine. Install on both hot and cold water supply lines. Lawn sprinklers. | C-L at least 12 inches above highest sprinkler or discharge outlet. Steam tables. | C-L at least six inches above flood level. Tanks and vats. | C-L at least six inches above flood level rim or line. Trough urinals. | C-L at least 30 inches above perforated flush pipe. Flush tanks. | Equip with approved ball cock. Where ball cocks touch tank water equip with vacuum breaker at least one inch above overflow outlets. Where ball cock does not touch tank water install ball cock outlet at least one inch above overflow outlet or provide vacuum breaker as specified above. Hose bibbs, where aspirators or ejectors could be connected. | C-L at least six inches above floodlevel of receptacle served. b. Where a potable water connection is made to a line, fixture, tank, vat, pump, or other equipment with a hazard of backflow or backsiphonage where the water connection is subject to backpressure, and an airgap cannot be installed, the manager of the water division may require the use of an approved reduced pressure principle backflow preventer. A partial list of such connections is shown in subsection (h)(10). (10) Partial list of cross-connections which may be subject to back-pressure. a. Chemical lines b. Dock water outlets c. Individual water supplies d. Industrial process waterlines e. Pressure tanks f. Pumps g. Steam lines h. Swimming pools i. Tank and vats, bottom inlets j. Hose bibbs (11) Water connections where an actual or potential backsiphonage hazard exists may in lieu of devices specified in subsection (h)(8)a be provided with a barometric loop. Barometric loops shall precede the point of connection. (12) The manager of the water division may authorize installation of approved, double check-double gate valve assemblies with test cocks as protective devices against backflow in connections between a potable water system and other fluid systems which present no significant health hazard in the judgment of the manager. (13) When a booster pump is used on a water pressure booster system and the possibility exists that a positive pressure of ten psi or less may occur on the suction side of the pump, there shall be installed a low-pressure cutoff on the booster pump to prevent the creation of a vacuum or negative pressure on the suction side of the pump, thus cutting off water to other outlets.
Ask a question about Springfield law
Corpus searches the Springfield sections it holds and shows the ones that match, with their citations. Free, no sign-in.