§ 9.24.050 — Requirements and policy
Code of Ordinances, City of Bloomington, Indiana (Supp. No. 51, Update 1: codified through Ordinance No. 2026-15, passed July 17, 2026) · Bloomington Municipal Code § 9.24.050
Corpus is an independent public-information project, not the official City of Bloomington website. Stable reference: corpuslaw.us/code/b26f7685-72d8-4ec0-b636-e9749f7398bf
9.24.050 - Requirements and policy.
(a) No new or existing water service connection to any premises shall be installed or maintained unless the water supply is protected as required by City of Bloomington laws and regulations and this chapter. Service of water to any premises shall be discontinued by CBU if a backflow prevention assembly required by this chapter is not installed, tested and maintained, or if it is found that a backflow prevention assembly has been removed, bypassed, or if an unprotected cross connection exists on the premises. Service will not be restored until such conditions or defects are corrected. (b) The customer's system shall be open for inspection or testing of cross connection control devices at all times to authorized representatives of CBU to determine whether unprotected cross connections or other structural or sanitary hazards, including violations of these regulations, exist. When such a condition becomes known, the director may deny or immediately discontinue service to the premises by providing for a physical break in the service line until the customer has corrected the condition(s) in conformance with the City of Bloomington statutes relating to plumbing and water supplies and the regulations adopted pursuant thereto. (c) An approved backflow prevention assembly shall also be installed on each service line to a customer's water system after the water meter and immediately inside the building being served, before the first branch line leading off the service line, wherever the following conditions exist: (1) In the case of premises having an auxiliary water supply which is not or may not be of safe bacteriological or chemical quality and which is not acceptable as an additional source by the director, the public water system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line(s) commensurate with the degree of hazard. (2) In the case of premises that are designated cross connection hazards on which any industrial fluids or any other objectionable substance is handled in such a fashion as to create an actual or potential hazard to the public water system, the public system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line(s) commensurate with the degree of hazard. This shall include the handling of process waters and waters originating from CBU's system which have been subject to deterioration in quality. (3) In the case of premises having internal cross connections that cannot be permanently corrected or protected against, or intricate plumbing and piping arrangements, or where entry to all portions of the premises is not readily accessible for inspection purposes, making it impracticable or impossible to ascertain whether or not dangerous cross connections exist, the public water system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line(s). (4) In the case of premises where a cross connection has resulted in a contaminant being introduced into a public or customer water system, the public water system shall be protected against backflow from the premises by installing an approved backflow prevention assembly in the service line(s). (5) In the case of premises that have a land irrigation facility buried below ground that has a sprinkler outlet located less than six inches above grade, the public water supply shall be protected by installing an approved backflow prevention assembly in the service line. (6) In the case of hydrant usage other than firefighting or flushing, the public water supply shall be protected by installing an approved backflow prevention assembly in the service line. Use of hydrants other than firefighting or flushing are prohibited, unless authorized by the director. (d) The type of protective assembly required shall depend upon the degree of hazard which exists as follows: (1) In the case of any premises where there is an auxiliary water supply as stated in subsection (c)(1) of this section and it is not subject to any of the following rules, the public water system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly. In the case of surface water auxiliary supply, the public water system must be protected by an approved air gap. (2) In the case of any premises where there is water or substance that would be objectionable but not hazardous to health, if introduced into the public water system, the public water system shall be protected by an approved double check valve backflow prevention assembly as determined by CBU. (3) In the case of any premises where there is any material dangerous to health, which is handled in such a fashion as to create an actual or potential hazard to the public water system, the public water system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly. (4) In the case of any premises where there are unprotected cross connections, either actual or potential, the public water system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly at the service connection. (5) In the case of any premises where, because of security requirements or other prohibitions or restrictions, it is impossible or impractical to make a complete in-plant cross connection survey, the public water system shall be protected against backflow from the premises by either an approved air gap or an approved reduced pressure principle backflow prevention assembly on each service line to the premises. (6) In the case of any premises where there is an irrigation facility buried below ground that has a sprinkler outlet located less than six inches above grade, the public water supply shall be protected by an air gap, a pressure type vacuum breaker, or a reduced pressure principle backflow preventer on the service line to the premises. (7) In the case of hydrant usage other than firefighting or flushing, the public water supply shall be protected by installing an air gap in the service line. Use of hydrants other than firefighting or flushing are prohibited, unless authorized by the director. (e) Any backflow prevention assembly required herein shall be of a make, model and size approved by the director and shall be installed in a location that allows access to the device for maintenance and testing from floor level without the use of a ladder. The device shall not be installed below ground grade level and must not be subject to flooding, excessive heat, or freezing temperatures. (f) It shall be the duty of the customer at any premises where backflow prevention assemblies are installed to have a field test performed upon installation and thereafter at least once per calendar year. These tests shall be at the expense of the customer and shall be performed by a cross connection control device inspector registered in the state of Indiana. These assemblies shall be repaired, overhauled or replaced at the expense of the customer whenever said assemblies are found to be defective. Records of such tests, repairs and overhauls shall be kept for a minimum of three years and submitted as determined by the director to CBU within thirty days of testing. (g) All presently installed backflow prevention assemblies, which do not meet the requirements of this section but were approved devices for the purposes described herein at the time of installation and which have been properly maintained, shall, except for the field testing and maintenance requirements, be excluded from the requirements of these rules so long as the director is assured that they will satisfactorily protect the public water supply. The backflow prevention assembly shall be replaced by an approved backflow prevention assembly meeting the requirements of this section whenever: (1) The customer service line is modified; (2) A higher capacity meter is installed; (3) The premises is remodeled; (4) The existing device is moved from the present location; (5) The existing device requires more than minimum maintenance; (6) The director finds that the maintenance constitutes a hazard to health. (h) The director is authorized to make all necessary and reasonable rules and policies with respect to the enforcement of this chapter.
(Ord. No. 18-27, § 1, 12-19-2018)
Ask a question about Bloomington law
Corpus searches the Bloomington sections it holds and shows the ones that match, with their citations. Free, no sign-in.